INSP-Final Inspection | 1/2/2007 | 1/3/2007 | 1/3/2007 | P | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Final Inspection | 7/7/2006 | 7/10/2006 | 7/10/2006 | A | FAIL |
Troy Cobbley
|
|
|
Provide map at the facp, fix the pone line one and phone line two reporting, outside alarm bell can not be silenced by the facp and provide atleast 8.3 ah battery for the facp.
|
FIR-Aging Inspection | 4/13/2006 | 4/13/2006 | 4/18/2006 | | NR |
Troy Cobbley
|
|
|
Per Bill with Peak Alarm the work has not been completed yet.
|
Issue and Print Permit | | | 1/12/2006 | | DONE |
|
|
|
|
Alarm Plan Check | | | 1/4/2006 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/4/2006 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 1/4/2006 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 1/4/2006 | | 1/4/2006 | | DONE |
|
|
|
|
Telephone call | | | 1/4/2006 | | DONE |
|
|
|
Left message that permit is ready & fees///1/4/06 @1:40pm BAS
|
Alarm Plan Check | | | 10/10/2005 | | FAIL |
|
|
|
Phone call to Greg at Farren. Need the additional information.
1) solenoid valve current added to calculation.
2) solenoid valve part number for compatibility
3) pressure switch on potter.
|
Plan resubmittals received | | | 9/30/2005 | | DONE |
|
|
|
|
Case Summary | | | 9/30/2005 | | DONE |
|
|
|
|
Alarm Plan Check | | | 9/22/2005 | | FAIL |
|
|
|
Resubmittal required. Per comments discussed in a meeting.
|
Meeting | | | 9/22/2005 | | DONE |
|
|
|
Meeting to discuss the pre-action panel configuration.
|
Case Summary | | | 9/8/2005 | | DONE |
|
|
|
|
Application received | | | 9/8/2005 | | |
|
|
|
|
Plan assigned to (Mary) | 9/8/2005 | | | | |
|
|
|
|