Permit Information
Permit NumberFIR05-00594
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 950 W BANNOCK ST
Project NameSPR 10TH & BANNOCK PHASE 1
Customer Number 
ePlanReview 
Description
10TH & BANNOCK BUILDING (SHELL & CORE ) - To install 2 connected underground sealed concrete reservoir (4,678 gpm & 10,322 gpm) tanks connected with a combined capacity of 15,000 gallons (13,800 usable), a 4" fill line with related operating equipment/devices and appurtenance, one 125 hp, 750 gpm (457 rated head) at 225 psi, 9 stage Electric Vertical Shaft Turbine Fire Pump and a 3 hp Vertical In-line Jockey pump w/controller packages, a wet Automatic Class 1 standpipe system in the east and west stairwells (w/east the stairs incorporating a combination sprinkler/standpipe floor zone wet system piping and appurtenance), 1st floor wet zone system and an anti-freeze system for the Drive-Thru. All installed in a new 182,950-ft/2, twelve story concrete and steel framed office and retail, w/parking, high rise shell and core building. This is permitted work is attached to the shell and core building only and no occupancy is allowed under this permit. Underground fire service supply is constructed under FIR05-00349 (attached under the same shell building permit). All fire sprinkler tank, underground, overhead standpipe and related work shall comply with the IFC-2003, NFPA 13-2002, 14-2003, 20-2002, 22-2003, 24-2002, the attached review comments/conditions list, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this permitted work, to provide witness of compliance verification of meeting minimum code. This permit is attached to building permit: BLD05-02348.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/28/20064/28/20064/28/2006PPASS
DetailsForrest France
Fire sprinkler passed final inspection, permit finaled.
INSP-Final Inspection4/24/20064/24/20064/24/2006PPART
DetailsForrest France
Need to remove "construction caps" at the pendent heads in the showers on the 1st floor, install missing escutcheons at some locations.
INSP-Final Inspection4/17/20064/18/20064/18/2006PFAIL
DetailsForrest France
Stairway sprinklers must be installed per NFPA 13 2002 8.14.3.2.1.
INSP-Final Inspection4/14/20064/17/20064/17/2006ADEFR
DetailsForrest France
Inspection rescheduled
Inspection Record Card- Fire4/12/2006 4/12/2006 DONE
Inspection Record Card- Fire4/12/2006 4/12/2006 DONE
Permit Ready to Issue  4/12/2006 DONE
Issue and Print Permit  4/12/2006 DONE
Plan resubmittals received  4/10/2006  
Plan assigned to (SAM)4/10/2006 4/10/2006 PASS
Plan mod - quick review. Faxed plan revisions to add 3 sprinklers in elevator shafts (1 each shaft), one additional sprinkler in enlarged elevator equipment room, and 1 head in new vestibule room at stairwell entrance on penthouse level. No calc's; piping layout hydraulically similar to issued approved plans. Revised stamped plans taken to permit desk to be issued with resubmittal fee.
PLANS/APPL TAKEN TO FRONT DESK  4/10/2006  
INSP-Sprinkler Rough-in4/6/20064/6/20064/6/2006PPART
DetailsForrest France
The 11th floor overhead rough-in is good for cover at the drop ceiling areas.
INSP-Sprinkler Rough-in4/4/20064/4/20064/4/2006PPART
DetailsForrest France
Performed standpipe flow test as required.
INSP-Sprinkler Rough-in3/30/20063/31/20063/31/2006APASS
DetailsTroy Cobbley
sprinkler piping in the lower ceilings on the first floor are ok to cover. See city approved plans for locations . The west side lower ceiling has a lower soffit that will require an additional sprinkler head to provide proper coverage. Also marked on plans.
INSP-Sprinkler Rough-in/Hydro3/28/20063/29/20063/29/2006PPART
DetailsForrest France
Hydrostatic test of the overhead wet, antifreeze, and standpipe systems is satisfactory, noted one head at the mezzanine stair landing is painted, head cage is missing at head under mezz ductwork, inspected the 5th and 6th floors for cover, the mech penthouse, 11th floor, and portions of the 1st floor are not inspected for cover at this time, discussed items left for completion at the riser room and final testing including standpipe flow test, forward flow of BFP and related sprinkler alarms.
INSP-Sprinkler Rough-in3/24/20063/28/20063/28/2006APART
DetailsForrest France
Pump start-up testing performed with manufacturer rep. including churn, rated and 150 percent capacity, manual and automatic starts and stops, jockey pump, set pressures, event log, min. run time, sensing lines, piping arrangements. Performance testing only, no alarm, trouble or supervised conditions tested at this time.
INSP-Sprinkler Rough-in3/22/20063/27/20063/27/2006PPART
DetailsForrest France
Overhead rough-in is good for cover on floors 10, 9, 8, and 7. Partial inspection of floor 5 as ceiling grid is not complete. Floor 6 and 11 not ready for cover inspection at this time. Also concluded satisfactory 72 hr hydro test of the UG tanks as water level did not drop.
INSP-Sprinkler Rough-in3/23/20063/24/20063/24/2006PPART
DetailsForrest France
Begin 72hr test of the water level at the underground storage tanks.
INSP-Sprinkler Rough-in3/16/20063/17/20063/17/2006PPART
DetailsForrest France
Third and fourth floor overhead rough-in is acceptable for cover.
INSP-Sprinkler Rough-in3/14/20063/15/20063/15/2006APART
DetailsForrest France
Core areas including the restrooms,elevator lobby, and janitors closet on the 7th-11th floors inspected for rough-in cover, 2nd and 1st floors rough-in is good for cover, one head in the ATM room is blocked by ductwork, discussed hydro testing schedule.
INSP-Supply line flush3/13/20063/14/20063/14/2006ADEFR
DetailsForrest France
This inspection request was intended for an UG supply line flush under project related permit FIR05-00395-contractor called in the wrong permit number (for overhead), flush was witnessed and performed satisfactory.
INSP-Sprinkler Rough-in/Hydro2/28/20063/1/20063/1/2006APART
DetailsForrest France
Overhead rough-in is good for cover at the 2nd thru 6th floor core areas including restrooms, elevator lobby, janitors closets, tele rooms and electrical rooms, discussed inspection method for the common floor areas, also inspected corridors and adjacent meeting rooms at the 2nd floor.
INSP-Sprinkler Rough-in/Hydro2/27/20062/28/20062/28/2006PCANC
DetailsForrest France
Inspection to be rescheduled due to time constraints.
Sprinkler Plan Check2/8/2006 2/24/2006 PASS
DetailsBill Alexander
Override - Parcel Holds  2/24/2006  
Inspection Record Card- Fire2/24/2006 2/24/2006 DONE
Override - Parcel Holds  2/24/2006  
Permit Ready to Issue  2/24/2006 DONE
Telephone call  2/24/2006 DONE
lft vm with gerald ###-#### that permit and fees are ready to be picked up
Issue and Print Permit  2/24/2006 DONE
Plan assigned to (Bill)1/13/2006 2/24/2006 DONE
DetailsBill Alexander
CHANGE STATUS TO (ISS)  2/24/2006  
INSP-Sprinkler Rough-in2/13/20062/14/20062/14/2006ADONE
DetailsForrest France
On site confrence to discuss location of the penthouse mechanical room standpipe hose connections.
INSP-Sprinkler Rough-in2/13/20062/13/20062/13/2006PCANC
DetailsForrest France
Inspection was intended for the UG rough-in under a different permit.
INSP-Supply line flush2/10/20062/10/20062/13/2006PNR
DetailsForrest France
Per contractor, not ready for inspection, to be rescheduled for next week.
INSP-Sprinkler Rough-in2/9/20062/9/20062/10/2006PFAIL
DetailsTroy Cobbley
Inspection was for the lining of the tank. Provide access to the interior of the tank for inspection
Plan resubmittals received  2/8/2006 DONE
CHANGE STATUS TO (ISS)  2/8/2006 DONE
Sprinkler Plan Check1/13/2006 2/7/2006 PART
DetailsBill Alexander
Plan correction/resubmittal required
ITEM #32. Plan FP-6. An enclosed "canopy" (addressed as such by the designer on Plan FP-6) with one east face opening, located on the 2nd floor, is referenced with no protection incorporating 8.14.7.2, a "Canopy" sprinkler exemption: "Sprinklers shall be permitted to be omitted where the canopy or roof is of noncombustible or limited combustible construction." Per the Building Code, IBC 202 Canopy definition is: "An architectural projection that provides weather protection, identity or decoration and is supported by the building to which it is attached and at the outer end by not less than on stanchion. A canopy is comprised of a rigid structure over which a covering is attached." The area in questions does not apply for this exemption. This facility requires full fire sprinkler protection of which this area is part of part of and will require fire sprinkler protection. Revise and resubmit fire sprinkler protection plans meeting full sprinkler protection.
February 7, 2006 - Designer provided a personal letter from "Gary Christensen" (The Christensen Corporation), of which the response does not address an allowable code exemption for the same. Provide fire sprinkler protection and resubmit for approval.
Plan assigned to (Bill)2/6/2006 2/7/2006 DONE
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  2/7/2006 DONE
Inspection Record Card- Fire2/7/2006 2/7/2006 DONE
Telephone call  2/7/2006 DONE
called ###-#### and told Gerald that permit ready for pickup and is charged another $105
Permit Ready to Issue  2/7/2006 DONE
INSP-Sprinkler Rough-in2/3/20062/6/20062/6/2006APART
DetailsForrest France
First floor entry lobby hard lid area inspection only, acceptable to cover at this location only. The 1 1/4 branch line to feed the elevator pit sprinklers has not been installed.
Plan resubmittals received  2/3/2006 DONE
Case Summary  2/3/2006 DONE
Issue and Print Permit  2/2/2006 DONE
Plan assigned to (Bill)1/17/2006 2/1/2006 DONE
PLANS/APPL TAKEN TO FRONT DESK  2/1/2006 DONE
Permit Ready to Issue  2/1/2006 DONE
Telephone call  2/1/2006 DONE
left mess that is permit is ready
Plan resubmittals received  1/13/2006 DONE
INSP-Sprinkler Rough-in1/12/20061/12/20061/12/2006PPART
DetailsForrest France
Inspected four restrooms on the first floor for overhead rough-in cover.
INSP-Sprinkler Rough-in1/4/20061/4/20061/4/2006PPART
DetailsForrest France
Inspection for rough-in at 2nd floor hard lid area, sprinklers at ceiling pocket areas must comply with the requirements of note #137 on plan review documents. The updated approved resubmitted plans are required for future overhead inspection requests.
Sprinkler Plan Check  12/28/2005 FAIL
Plans had been held pending resubmited information. The information never arrived. I spoke to Gerald and he stated that they are going to resubmit the entire package due to changes. He stated that he didn't want the old copies returned. I faxed my review comments to him.
Sprinkler Plan Check11/22/2005 11/22/2005 FAIL
Plans review comments faxed to Gerald at Treasure Valley Fire Protection. This is the third review.
Plan resubmittals received  10/31/2005 DONE
(F) Reprint permit  10/12/2005 DONE
CHANGE STATUS TO (ISS)  10/12/2005 DONE
Sprinkler Plan Check9/29/2005 10/11/2005 PART
DetailsBill Alexander
The data has been moved to a Word document attached to this case.
Plan assigned to (Bill)9/29/2005 10/11/2005 DONE
PLANS/APPL TAKEN TO FRONT DESK  10/11/2005 DONE
Inspection Record Card- Fire10/11/2005 10/11/2005 DONE
Permit Ready to Issue  10/11/2005 DONE
Telephone call  10/11/2005 DONE
left mess that permit is ready
Issue permit  10/3/2005  
Plan assigned to (Bill)9/9/2005 9/29/2005 DONE
Sprinkler Plan Check9/9/2005 9/29/2005 PASS
DetailsBill Alexander
Plans approved with comments
PLANS/APPL TAKEN TO FRONT DESK  9/29/2005 DONE
Permit Ready to Issue  9/29/2005 DONE
Inspection Record Card- Fire9/29/2005 9/29/2005 DONE
Telephone call  9/29/2005 DONE
left mess that permit is ready
Miscellaneous action  9/27/2005 DONE
Approval granted to written request from G. Ebleling, TVFP to start work prior to issuance of this permit due to current time delay in approvals; faxed approval back to TVFP.
Plan resubmittals received  9/23/2005  
Application received  9/9/2005