INSP-Final Inspection | 12/21/2005 | 12/22/2005 | 12/22/2005 | A | PASS |
Forrest France
|
|
|
Resubmittals verified, duct detectors tested okay, fire alarm final inspection passed.
|
INSP-Final Inspection | 12/20/2005 | 12/21/2005 | 12/21/2005 | A | NR |
Forrest France
|
|
|
Per contractor job is not ready for inspection, work is incomplete.
|
Inspection Record Card- Fire | 12/16/2005 | | 12/16/2005 | | DONE |
|
|
|
|
Telephone call | | | 12/16/2005 | | DONE |
|
|
|
left mess that permit is ready
|
CHANGE STATUS TO (ISS) | | | 12/16/2005 | | DONE |
|
|
|
|
(F) Reprint permit | | | 12/16/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 12/16/2005 | | DONE |
|
|
|
|
Alarm Plan Check | | | 12/15/2005 | | PASS |
|
|
|
Plan Modification. Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/15/2005 | | DONE |
|
|
|
|
Plan resubmittals received | | | 12/9/2005 | | |
|
|
|
|
Miscellaneous action | | | 12/8/2005 | | DONE |
|
|
|
Received fax for the magnahelic testing of all duct detectors. They appear to be within the functional limits of the specs.
Inspection and testing may be scheduled.
|
INSP-Final Inspection | 11/22/2005 | 11/22/2005 | 11/22/2005 | A | PART |
Forrest France
|
|
|
Inspection to be performed by M. Froemke. Resubmittals are required as the Plan Modification approved submittal does not match the installed system.
Tested all items except the duct and in-duct detctors. (Requested magnehelic test on all duct detectors as locations are in the 90's of the duct work.)
|
INSP-Final Inspection | 11/21/2005 | 11/22/2005 | 11/22/2005 | A | DEFR |
Forrest France
|
|
|
Inspection to be performed by M. Froemke.
|
INSP-Final Inspection | 11/21/2005 | 11/21/2005 | 11/21/2005 | P | DEFR |
Forrest France
|
|
|
Inspection scheduled for 11/22 am per agreement.
|
INSP-Final Inspection | 11/18/2005 | 11/18/2005 | 11/18/2005 | P | CANC |
Forrest France
|
|
|
No time for an inspection, however while on site for a sprinkler inspection noticed two AV's are below the 80" min height AFF.
|
Issue permit | | | 11/18/2005 | | DONE |
|
|
|
|
Alarm Plan Check | | | 11/17/2005 | | PASS |
|
|
|
Plan Modification. Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/17/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 11/17/2005 | | 11/17/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 11/17/2005 | | DONE |
|
|
|
|
Telephone call | | | 11/17/2005 | | DONE |
|
|
|
Left message for Jason that permit is ready & fees///11/17/05 3:00pm BAS
|
INSP-Final Inspection | 11/3/2005 | 11/4/2005 | 11/4/2005 | P | CANC |
Forrest France
|
|
|
No inspection performed due to pending resubmittals for significant changes in actual install from approved plans per alarm plans examiner.
|
Plan resubmittals received | | | 11/4/2005 | | |
|
|
|
|
Plan assigned to (Mary) | 9/9/2005 | | 10/13/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 10/13/2005 | | 10/13/2005 | | DONE |
|
|
|
|
Alarm Plan Check | | | 10/13/2005 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/13/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 10/13/2005 | | DONE |
|
|
|
|
Telephone call | | | 10/13/2005 | | DONE |
|
|
|
Left message for Jason that permit is ready & fees///10/13/05 9:10am BAS
|
Issue and Print Permit | | | 10/13/2005 | | DONE |
|
|
|
|
Plan resubmittals received | | | 10/6/2005 | | |
|
|
|
|
Alarm Plan Check | | | 9/22/2005 | | FAIL |
|
|
|
Faxed comments to Jason Minnick.
|
Application received | | | 9/9/2005 | | |
|
|
|
|
Case Summary | | | 9/9/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 12/16/2005 | | | | |
|
|
|
|