INSP-Conference | 3/16/2010 | 3/17/2010 | 3/17/2010 | P | DONE |
Forrest France
|
|
|
Permit expired per conversation with contractor.
|
DOC - Permit Expired | | | 3/17/2010 | | DONE |
Tisha Gallop
|
|
|
permit expired per Forrest France
|
Miscellaneous action | | | 3/12/2010 | | DONE |
|
|
|
Sent email requesting project status.
|
INSP-Final Inspection | 5/18/2009 | 5/18/2009 | 5/18/2009 | P | PART |
Forrest France
|
|
|
Activities indicate underground supply line flush has not been completed, permit cannot be finaled at this time.
|
INSP-Sprinkler Rough-in | 5/2/2006 | 5/2/2006 | 5/2/2006 | P | PART |
Forrest France
|
|
|
UG hydrostatic test passed inspection.
|
INSP-Sprinkler Rough-in | 2/8/2006 | 2/9/2006 | 2/9/2006 | A | PASS |
Troy Cobbley
|
|
|
underground tie in to the united water supply is ok to cover. The piping from united water is not the 6" as shown on the plans but is actually 4". This inspector could not verify the "dead man" used to secured the 6x4 reducer. Pictures were taken and shown to Bill Alexander of the assembly.
|
INSP-Sprinkler Rough-in | 1/17/2006 | 1/17/2006 | 1/17/2006 | P | PASS |
Troy Cobbley
|
|
|
underground supply piping is ok to cover
|
INSP-Sprinkler Rough-in | 11/2/2005 | 11/2/2005 | 11/2/2005 | P | PART |
Forrest France
|
|
|
Underground riser and 5' stub out only are acceptable to cover.
|
INSP-Sprinkler Rough-in | 10/31/2005 | 10/31/2005 | 10/31/2005 | P | CANC |
Troy Cobbley
|
|
|
Not ready yet per Sam.
|
Issue and Print Permit | | | 9/22/2005 | | DONE |
|
|
|
|
Case Summary | | | 9/21/2005 | | DONE |
|
|
|
We received a check from Treasure Valley check #63865 for this permit, but they need to pick up the plans.rad
|
Sprinkler Plan Check | 9/19/2005 | | 9/19/2005 | | PASS |
|
|
|
plan approved as annoted in "red" without written comments subject to satisfactory final inspection.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/19/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 9/19/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 9/19/2005 | | 9/19/2005 | | DONE |
|
|
|
|
Telephone call | | | 9/19/2005 | | DONE |
|
|
|
Spoke with Jeff and told him that permit is ready & fees///9/19/05 2:20pm BAS
|
Application received | | | 9/13/2005 | | |
|
|
|
|
Plan assigned to (Bill) | 9/13/2005 | | | | |
|
|
|
|