Permit Information
Permit NumberFIR05-00605
StatusFinaled
Name ALARMCO
Site Address 6042 W PORT LN
Project Namealm-Davenport Vill 4plex lot14
Customer Number 
ePlanReview 
Description
To provide a sprinkler monitoring system in each apartment building (two total).

FIR05-00606 is associated with building permit (BLD 05-01374) and is to construct a new 3,804-ft/2, two story, four unit apartment building, each unit is two bedroom and has a separate entry and is two stories. The Type "A" unit has two full bathrooms and is 989-ft/2 Type "B" unit one and one half bathrooms and is 913-ft/2. An NFPA 13R fire sprinkler protection system is required for compensation for the lack of Fire Department access per 503.1.1, Exception 1. All construction per the approved plans and attached comment list. MJP DRH 04-00190 CUP 04-00048. (Lot18)

FIR05-00605 is associated with building permit (BLD 05-01400) and is to construct a new 3,804 sq.ft. two story, four unit apartment building, each unit is two bedroom and has a separate entry and is two stories. The Type "A" unit has two full bathrooms and is 989 sq.ft. the Type "B" unit one and one half bathrooms and is 913 sq.ft. An NFPA 13R fire sprinkler protection system is required for compensation for the lack of Fire Department access per 503.1.1, Exception 1. All construction per the approved plans and attached comment list. MJP DRH 04-00190 CUP 04-00048. (Lot 14)
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/27/20061/27/20061/27/2006PPASS
DetailsTroy Cobbley
permit finaled
Issue and Print Permit  1/27/2006 DONE
Alarm Plan Check  1/27/2006 PASS
Plan Modification. Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  1/27/2006 DONE
Permit Ready to Issue  1/27/2006 DONE
Telephone call  1/27/2006 DONE
lft ms with secretry (alan mannor was off) that permit and no fee ready to be picked up
Plan resubmittals received  1/13/2006  
Case Summary  1/13/2006 DONE
INSP-Final Inspection1/10/20061/10/20061/10/2006PFAIL
DetailsTroy Cobbley
Monitoring not set up. No tampers on the two control valves. Per notes plans need to be resubmitted for the additional valve.
Issue permit  1/10/2006 DONE
Inspection Record Card- Fire9/28/2005 9/28/2005 DONE
Permit Ready to Issue  9/28/2005 DONE
Inspection Record Card- Fire9/28/2005 9/28/2005 DONE
Telephone call  9/28/2005 DONE
left mess that permit is ready
Plan assigned to (Mary)9/15/2005 9/26/2005 DONE
Alarm Plan Check  9/26/2005 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  9/26/2005 DONE
Telephone call  9/23/2005 DONE
Talked to Bill at Alarmco, I stated I needed the manufacturer's cut sheet that defines the maximum battery charging capacity and the maximum size battery that will fit in the panel.
Plan resubmittals received  9/23/2005 DONE
Received manufacturer's cut sheets
Case Summary  9/15/2005 DONE
Application received  9/15/2005