INSP-Final Inspection | 4/18/2006 | 4/18/2006 | 4/18/2006 | P | PASS |
Forrest France
|
|
|
Fire alarm finaled.
|
INSP-Final Inspection | 11/30/2005 | 12/1/2005 | 12/1/2005 | A | PART |
Forrest France
|
|
|
Fire alarm for this permit is acceptable, corrections have been completed, final pending shell alarm finals wip.
|
Alarm Plan Check | | | 11/30/2005 | | PASS |
|
|
|
Plan Modification. Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/30/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 11/30/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 11/30/2005 | | 11/30/2005 | | DONE |
|
|
|
|
Telephone call | | | 11/30/2005 | | DONE |
|
|
|
spoke with Rob and told him permit is ready & no fees///11/30/05 @ 10:40am BAS
|
CHANGE STATUS TO (ISS) | | | 11/30/2005 | | DONE |
|
|
|
re-issued
|
INSP-Final Inspection | 11/29/2005 | 11/29/2005 | 11/29/2005 | P | DEFR |
Forrest France
|
|
|
Need updated plans showing added strobe, will verify supply air has been ducted to avoid mixing air in return at final inspection.
|
Plan resubmittals received | | | 11/16/2005 | | DONE |
|
|
|
|
INSP-Final Inspection | 11/2/2005 | 11/4/2005 | 11/4/2005 | P | FAIL |
Forrest France
|
|
|
Grant Ahten; Phone #: ###-#### Internet Inspection Request from: Terry Owsley
1) Need to add an additional strobe in reception area because of the column that blocks the 95 cd in the ceiling.
2) Duct detectors are installed in the return of the HP units, but the OSA is dumped into the return plenum, whereby the duct detector is actually monitoring "mixed" air.
|
Issue permit | | | 10/5/2005 | | DONE |
|
|
|
|
Plan assigned to (Mary) | 9/16/2005 | | 9/23/2005 | | DONE |
|
|
|
|
Alarm Plan Check | | | 9/23/2005 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 9/23/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 9/23/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 9/23/2005 | | 9/23/2005 | | DONE |
|
|
|
|
Case Summary | | | 9/16/2005 | | DONE |
|
|
|
|
Application received | | | 9/16/2005 | | |
|
|
|
|