Permit Information
Permit NumberFIR05-00609
StatusFinaled
Name PROTEX
Site Address 121 N 9TH ST Unit: 302
Project Namealm - PLAZA 121
Customer Number 
ePlanReview 
Description
Fire alarm permit FIR04-00658 (shell and core) must be completed prior to occupancy for this permit (FIR05-00229).

To provide total notification and four (4) duct smoke detectors and relay modules for HVAC shutdown to the new TI space located on the third floor. The required manual fire alarm system includes sprinkler monitoring, HVAC shutdown, elevator recall/shutdown and notification throughout.

The associated building permit (BLD 05-02001) is to finish a 2,401 square foot tenant space located on the 3rd floor of an existing 76,680 square foot, 6 story building. This permit is for a "vanilla finish". The name of the tenant has not been disclosed. A separate permit is required for occupancy. Work is to include interior nonbearing walls and finishes. The work shall comply with the approved drawings, the plan review report, and all applicable codes. The fire sprinkler system shall comply with NFPA 13 as regulated by the Fire Department. **CJW** NO TENANT - VANILLA FINISH - PLAZA 121 - STE 302) This building is fire sprinklered.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/18/20064/18/20064/18/2006PPASS
DetailsForrest France
Fire alarm finaled.
INSP-Final Inspection11/30/200512/1/200512/1/2005APART
DetailsForrest France
Fire alarm for this permit is acceptable, corrections have been completed, final pending shell alarm finals wip.
Alarm Plan Check  11/30/2005 PASS
Plan Modification. Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  11/30/2005 DONE
Permit Ready to Issue  11/30/2005 DONE
Inspection Record Card- Fire11/30/2005 11/30/2005 DONE
Telephone call  11/30/2005 DONE
spoke with Rob and told him permit is ready & no fees///11/30/05 @ 10:40am BAS
CHANGE STATUS TO (ISS)  11/30/2005 DONE
re-issued
INSP-Final Inspection11/29/200511/29/200511/29/2005PDEFR
DetailsForrest France
Need updated plans showing added strobe, will verify supply air has been ducted to avoid mixing air in return at final inspection.
Plan resubmittals received  11/16/2005 DONE
INSP-Final Inspection11/2/200511/4/200511/4/2005PFAIL
DetailsForrest France
Grant Ahten; Phone #: ###-#### Internet Inspection Request from: Terry Owsley

1) Need to add an additional strobe in reception area because of the column that blocks the 95 cd in the ceiling.

2) Duct detectors are installed in the return of the HP units, but the OSA is dumped into the return plenum, whereby the duct detector is actually monitoring "mixed" air.
Issue permit  10/5/2005 DONE
Plan assigned to (Mary)9/16/2005 9/23/2005 DONE
Alarm Plan Check  9/23/2005 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  9/23/2005 DONE
Permit Ready to Issue  9/23/2005 DONE
Inspection Record Card- Fire9/23/2005 9/23/2005 DONE
Case Summary  9/16/2005 DONE
Application received  9/16/2005