INSP-Final Inspection | 3/9/2006 | 3/14/2006 | 3/14/2006 | A | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 2/28/2006 | 3/2/2006 | 3/2/2006 | A | FAIL |
Forrest France
|
|
|
Fire sprinkler must meet requirements of NFPA 13 2002 7.3.2.4 (3) with respect to the installation of pendent sprinklers on preaction systems.
|
INSP-Final Inspection | 2/22/2006 | 2/23/2006 | 2/23/2006 | A | CANC |
Forrest France
|
|
|
Cancel inspection due to pipe hanger issues as discussed on site.
|
Sprinkler Plan Check | 2/17/2006 | | 2/22/2006 | | PASS |
Bill Alexander
|
|
|
IFC Fire/Life Safety Inspector shall verify correct hanger meeting requirements of IBC 102.4, 102.7, 102.8, 104.7.2, 105.4.2, 1604.3, 1604.4, NFPA 13:9.1.1.2.
|
Plan resubmittals received | | | 2/17/2006 | | |
Bill Alexander
|
|
|
|
Plan assigned to (Bill) | 9/19/2005 | | 10/10/2005 | | DONE |
Bill Alexander
|
|
|
|
Sprinkler Plan Check | 9/16/2005 | | 10/10/2005 | | PASS |
Bill Alexander
|
|
|
In office review-plans given to Troy to return to Micron for inspection reference.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/10/2005 | | DONE |
|
|
|
|
Issue and Print Permit | | | 10/10/2005 | | DONE |
|
|
|
|
Application received | | | 9/19/2005 | | DONE |
|
|
|