INSP-Final Inspection | 3/19/2007 | 3/20/2007 | 3/20/2007 | A | PASS |
Forrest France
|
|
|
Corrections verified, fire alarm passed inspeciton, permit finaled.
|
INSP-Final Inspection | 2/27/2007 | 2/28/2007 | 2/28/2007 | A | FAIL |
Forrest France
|
|
|
Doors at one location will need repair for proper closure upon smoke detection.
|
INSP-Final Inspection | 10/30/2006 | 11/1/2006 | 11/1/2006 | A | PART |
Forrest France
|
|
|
Per inspection by M. Timmerman the AV portion of this work passed inspeciton.
|
FIR-Aging Inspection | 8/10/2006 | 8/10/2006 | 8/15/2006 | | DEFR |
Forrest France
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/13/2006 | | DONE |
|
|
|
|
Issue and Print Permit | | | 1/13/2006 | | DONE |
|
|
|
|
Plan resubmittals received | | | 1/12/2006 | | DONE |
|
|
|
Received revised riser.
|
Alarm Plan Check | | | 1/12/2006 | | PASS |
|
|
|
Approved pending PDS Fire Inspector field verification. No comments written.
|
Alarm Plan Check | | | 11/23/2005 | | FAIL |
|
|
|
Plans do not match riser. Upon correcting the riser, please verify battery (BPS calc still does not include supervisory current for the panel) and voltage drop calculations.
This submittal appears to include more than one "C" number. This is acceptable as long as the changes are identified by the appropriate "C" number.
|
Alarm Plan Check | | | 11/14/2005 | | FAIL |
|
|
|
Missing matrix
NAC panel calcs missing supervisory and alarm current.
FACP battery calc is incomplete (half omissing on the page) not shown on the plans.
Plans don't match riser.
Corridor 100AY, exiting H/S further than 15 feet form end of corridor.
Question mixing Genesis and 757 on same circuit, does this impact the syncing of strobes?
|
Plan assigned to (Mary) | 11/3/2005 | | 11/3/2005 | | DONE |
|
|
|
|
Application received | | | 9/19/2005 | | DONE |
|
|
|
This permit was created on the web by Paul Marcolina
|