INSP-Final Inspection | 6/27/2006 | 6/28/2006 | 6/28/2006 | A | PASS |
Forrest France
|
|
|
Items on correction notice have been verified for completion, inspection passed, permit finaled.
|
INSP-Final Inspection | 6/26/2006 | 6/26/2006 | 6/27/2006 | P | FAIL |
Forrest France
|
|
|
Need to replace one defective SW head at the garage area, repair leaking main drain connection, provide spare SW in head box.
|
INSP-Sprinkler Rough-in/Hydro | 1/20/2006 | 1/23/2006 | 1/23/2006 | A | PART |
Forrest France
|
|
|
Two areas as noted lack proper tenting, one head in the sauna room is not installed at this time, two heads have been added below the stairs adjacent to the riser, riser not complete, discussed coverage of the heating unit for the sauna, overhead rough-in is acceptable for cover as noted.
|
INSP-Sprinkler Rough-in | 1/19/2006 | 1/20/2006 | 1/20/2006 | P | CANC |
Forrest France
|
|
|
No time available for this inspection today, to be rescheduled for next week per conversation with contractor.
|
Sprinkler Plan Check | 11/14/2005 | | 11/14/2005 | | PASS |
Troy Cobbley
|
|
|
Resubmittals approved with comments
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/14/2005 | | DONE |
Troy Cobbley
|
|
|
|
Inspection Record Card- Fire | 11/14/2005 | | 11/14/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 11/14/2005 | | DONE |
|
|
|
|
Telephone call | | | 11/14/2005 | | DONE |
|
|
|
left mess that permit is ready
|
Issue and Print Permit | | | 11/14/2005 | | DONE |
|
|
|
|
Plan resubmittals received | | | 10/24/2005 | | DONE |
|
|
|
|
Case Summary | | | 10/24/2005 | | DONE |
|
|
|
|
Issue permit | | | 10/20/2005 | | DONE |
|
|
|
|
Case Summary | | | 10/18/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 10/17/2005 | | 10/17/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 10/17/2005 | | DONE |
|
|
|
|
Telephone call | | | 10/17/2005 | | DONE |
|
|
|
lft vm with trent bice ###-#### that permit and fees are ready to picked up
|
Plan assigned to (Bill) | 9/26/2005 | | 10/14/2005 | | DONE |
|
|
|
|
Sprinkler Plan Check | 6/29/2005 | | 10/14/2005 | | PART |
Bill Alexander
|
|
|
CORRECTIONS REQUIRED
1. Water supply certificate is not starting at the residential meter but at the supply connection! Revise calcs and plans that reflect complete and correct designs, (this means the piping from the supply tap to the meter will be addressed).
2. Provide a final sprinkler head analysis sheet with every calculation. This sheet shall be like all others Shilo has previously submitted. (No exceptions). (BMC 7-01-50-901.2, IFC 105.4.2)
3. Manufacturer data submittals shall be included for all listed devises installing Provide manufactures data submittals addressing the correct size and type backflow installing. (BMC 7-01-50-901.2, IFC 105.4.2)
4. The domestic control shall be connected upstream of the fire sprinkler take-off, (no exceptions). Revise and resubmit. (NFPA 13D:A.6.2[a], A.6.3[a])
5. The Standard Response, 5.0 K-factor pendant sprinkler installing in the sauna will not be allowed in this residential facility. Provide a Quick Response or a Fast-Response, 4.2 K-factor sprinkler. (NFPA 13D-7.5.1)
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/14/2005 | | DONE |
|
|
|
|
Application received | | | 9/26/2005 | | |
|
|
|
|