Permit Information
Permit NumberFIR05-00631
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 1734 S TOLUKA WAY
Project NameSPR BENNINON RESIDENCE
Customer Number 
ePlanReview 
Description
BENNION RESIDENCE * To install a life safety NFPA 13D system in a new four bedroom, two and three quarter bathroom 3867-ft/2 single story single family dwelling (2663-ft/2 first floor/1204-ft/2 Finished Basement) with the installation of a single row of dry sidewall sprinklers along the common walls attached to the attached 845-ft/2 three car garage and the living space. System shall be equipped with an alarm initiating device and an outside alarm. All fire sprinkler work and related, which includes dual use, single service water supply, the system backflow prevention device (provided by others), shall be per NFPA 13D, approved plans, engineering/red-lining and attached review comments, under direction of the Fire Chief. This permit is attached to: BLD05-02233.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/27/20066/28/20066/28/2006APASS
DetailsForrest France
Items on correction notice have been verified for completion, inspection passed, permit finaled.
INSP-Final Inspection6/26/20066/26/20066/27/2006PFAIL
DetailsForrest France
Need to replace one defective SW head at the garage area, repair leaking main drain connection, provide spare SW in head box.
INSP-Sprinkler Rough-in/Hydro1/20/20061/23/20061/23/2006APART
DetailsForrest France
Two areas as noted lack proper tenting, one head in the sauna room is not installed at this time, two heads have been added below the stairs adjacent to the riser, riser not complete, discussed coverage of the heating unit for the sauna, overhead rough-in is acceptable for cover as noted.
INSP-Sprinkler Rough-in1/19/20061/20/20061/20/2006PCANC
DetailsForrest France
No time available for this inspection today, to be rescheduled for next week per conversation with contractor.
Sprinkler Plan Check11/14/2005 11/14/2005 PASS
DetailsTroy Cobbley
Resubmittals approved with comments
PLANS/APPL TAKEN TO FRONT DESK  11/14/2005 DONE
DetailsTroy Cobbley
Inspection Record Card- Fire11/14/2005 11/14/2005 DONE
Permit Ready to Issue  11/14/2005 DONE
Telephone call  11/14/2005 DONE
left mess that permit is ready
Issue and Print Permit  11/14/2005 DONE
Plan resubmittals received  10/24/2005 DONE
Case Summary  10/24/2005 DONE
Issue permit  10/20/2005 DONE
Case Summary  10/18/2005 DONE
Inspection Record Card- Fire10/17/2005 10/17/2005 DONE
Permit Ready to Issue  10/17/2005 DONE
Telephone call  10/17/2005 DONE
lft vm with trent bice ###-#### that permit and fees are ready to picked up
Plan assigned to (Bill)9/26/2005 10/14/2005 DONE
Sprinkler Plan Check6/29/2005 10/14/2005 PART
DetailsBill Alexander
CORRECTIONS REQUIRED
1. Water supply certificate is not starting at the residential meter but at the supply connection! Revise calcs and plans that reflect complete and correct designs, (this means the piping from the supply tap to the meter will be addressed).

2. Provide a final sprinkler head analysis sheet with every calculation. This sheet shall be like all others Shilo has previously submitted. (No exceptions). (BMC 7-01-50-901.2, IFC 105.4.2)

3. Manufacturer data submittals shall be included for all listed devises installing Provide manufactures data submittals addressing the correct size and type backflow installing. (BMC 7-01-50-901.2, IFC 105.4.2)

4. The domestic control shall be connected upstream of the fire sprinkler take-off, (no exceptions). Revise and resubmit. (NFPA 13D:A.6.2[a], A.6.3[a])

5. The Standard Response, 5.0 K-factor pendant sprinkler installing in the sauna will not be allowed in this residential facility. Provide a Quick Response or a Fast-Response, 4.2 K-factor sprinkler. (NFPA 13D-7.5.1)
PLANS/APPL TAKEN TO FRONT DESK  10/14/2005 DONE
Application received  9/26/2005