Permit Information
Permit NumberFIR05-00644
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 7957 W SPECTRUM ST
Project NameSPR HOMEWOOD SUITES
Customer Number 
ePlanReview 
Description
(HOMEWOOD SUITES-HILTON HOTEL) To install a complete overhead fire sprinkler system consisting of a Class 1 manual standpipe system, one wet and two dry pipe systems, all connected to an underground supply permitted under FIR05-00509, in a new 102,196-ft/2, 4-story (with combustible attic cavities), wood framed, 110 guest room extended stay hotel with a restaurant, lodge area, indoor swimming pool and spa area. This facility has horizontal exits on each floor required for travel distance to the required exits. This building requires full fire sprinkler protection (NFPA 13 System) for area increase. The fire sprinkler system work shall comply with the IFC 2003, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD04-02035.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/7/20072/9/20072/9/2007PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection1/31/20072/1/20072/1/2007AFAIL
DetailsTroy Cobbley
No time to finish the sprinkler inspection today. The interconnection of the sprinkler devices with the fire alarm system passed. Both dry system have been trip tested. The first floor took 24 seconds for water to get to the inspectors test and the fourth floor took 41 seconds.
INSP-Sprinkler Rough-in/Hydro1/30/20071/31/20071/31/2007APASS
DetailsTroy Cobbley
24 hour air tests for both the dry systems has passed.
INSP-Sprinkler Rough-in/Hydro1/29/20071/30/20071/30/2007APASS
DetailsTroy Cobbley
The standpipe hydro test passed. Started the 24 hour air tests on both dry systems at 9:30. The 4th floor is at 45psi and the front system is at 47psi.
INSP-Sprinkler Rough-in/Hydro1/25/20071/26/20071/26/2007PPASS
DetailsTroy Cobbley
Hydro test passed. Still need to hydro test the standpipes and 24 hour tests for the dry systems.
INSP-Sprinkler Rough-in/Hydro1/11/20071/12/20071/12/2007APASS
DetailsTroy Cobbley
hydro test for the 1st, 2nd, 3rd and 4th floors has passed.
INSP-Conference11/16/200611/17/200611/17/2006APASS
DetailsTroy Cobbley
The conference was for the eaves. The eaves will have blown-in insulation and cardboard has been utilized to provide the necessary eave ventilation. Appears acceptable.
INSP-Conference10/27/200610/30/200610/30/2006ADONE
DetailsTroy Cobbley
I discussed combustible concealed space requirements with the fire sprinkler contractor and the builder
INSP-Conference10/12/200610/13/200610/13/2006ADONE
DetailsTroy Cobbley
fire place and the stairwell combustible concealed spaced have been filled with insulation and sheetrocked. I went over the combustible eaves with both the fire sprinkler contractor and the general contractor
INSP-Sprinkler Rough-in10/11/200610/12/200610/12/2006APASS
DetailsTroy Cobbley
The club house branchline piping located below the hard lids but above the lay ceiling passed. Prior to cover the armovers will need to be inspected. I notified the sprinkler contractor that the fireplace area and the stairwells will need to be opened up for verification that the combustible areas have met the exceptions as stated in NFPA 13 for areas not requiring sprinklers. Another potential problem are the combustible eave pockets.
INSP-Conference9/20/20069/20/20069/20/2006PDONE
DetailsTroy Cobbley
Contractor is installing fire resistant wood in the areas above the lobby ceiling. Hardlid is ok to cover.
INSP-Sprinkler Rough-in9/18/20069/18/20069/18/2006PFAIL
DetailsTroy Cobbley
Piping as installed is ok in main lobby area but wood has been installed above the ceiling. Do not cover piping until combustibles have been addressed.
INSP-Sprinkler Rough-in8/31/20069/1/20069/1/2006APART
DetailsForrest France
OH rough-in for the drop ceiling area above the pool as marked on approved plans is acceptable for cover.
INSP-Sprinkler Rough-in7/21/20067/24/20067/24/2006APASS
DetailsTroy Cobbley
The east half of the first floor is ok to cover. I also inspected the concealed pockets in the room entry ways and verified that they are indeed noncombustible.
Permit Ready to Issue  7/21/2006 DONE
per bill
Issue and Print Permit  7/21/2006 DONE
Telephone call  7/20/2006 DONE
spoke to brad@###-####/told permit was ready, permit#, prjt name & address, and fee due
Sprinkler Plan Check7/6/2006 7/20/2006 PASS
DetailsBill Alexander
Plan assigned to (Bill)7/20/2006 7/20/2006 DONE
PLANS/APPL TAKEN TO FRONT DESK  7/20/2006 DONE
INSP-Sprinkler Rough-in7/13/20067/14/20067/14/2006APASS
DetailsTroy Cobbley
North half of the first floor piping is ok to cover
INSP-Sprinkler Rough-in7/5/20067/5/20067/6/2006PPASS
DetailsTroy Cobbley
Pool area and lobby area dry system ok to cover. Combustible concealed eave spaces as marked on the plans for these same areas will need to be addressed prior to final
Plan resubmittals received  7/6/2006  
Case Summary  7/6/2006 DONE
INSP-Sprinkler Rough-in6/29/20066/30/20066/30/2006PPART
DetailsTroy Cobbley
Rough-in for the pool/clubhouse area is mostley passed. See approved plans for areas needing corrections. Branchlines have been added in areas not provided with protection. As-builts will need to be provided prior to cover. Combustible pockets still need protection. Branchlines in peak are too far down from the peak
INSP-Sprinkler Rough-in6/26/20066/27/20066/27/2006APASS
DetailsTroy Cobbley
2nd floor sprinkler piping ok to cover.
INSP-Sprinkler Rough-in6/23/20066/26/20066/26/2006AFAIL
DetailsTroy Cobbley
Pendant heads are still not spaced as discussed on the second floor. Sprinkler piping in the swimming area is not sized per plans and the upright sprinktler heads are not spaced per approved plans.
INSP-Sprinkler Rough-in6/23/20066/23/20066/23/2006PFAIL
DetailsTroy Cobbley
Almost all of the residence rooms have a single pendant head that is blocked by the stub wall. All of these pendants need to be relocated to be positioned as shown on the plans.
INSP-Sprinkler Rough-in6/14/20066/15/20066/15/2006APASS
DetailsTroy Cobbley
Fourth floor sprinkler piping is ok to cover. Some sidewall sprinkler heads are real close to being out of code compliance in regards to deflector distance from the ceiling, especially the heads in the mechanical closets in each room. Mark and I agreed these would be checked once the sheet rock patching was complete.
INSP-Sprinkler Rough-in6/6/20066/6/20066/6/2006PPASS
DetailsTroy Cobbley
The east wing of the 3rd floor is ok to cover.
INSP-Sprinkler Rough-in6/1/20066/2/20066/2/2006APASS
DetailsTroy Cobbley
The north wing of the third floor cpvc piping is ok to cover.
INSP-Sprinkler Rough-in6/1/20066/1/20066/1/2006PFAIL
DetailsTroy Cobbley
Inspection was for the north half of the 3rd floor which failed. there are multiple sprinkler heads and hangers overspaced. Inspection stopped.
INSP-Sprinkler Rough-in5/16/20065/17/20065/17/2006PPASS
DetailsTroy Cobbley
The remaining attic system passed rough-in inspection. Sprinkler coverage in the east catwalk area has been added and is being resubmitted for review. This work was not inspected
INSP-Sprinkler Rough-in4/28/20065/1/20065/1/2006APASS
DetailsTroy Cobbley
Per the sprinkler contractor the pockets behind the elevator shaft will be filled with insulation. Revised hydraulic calculations have been provided and field verified by me for the addition of one upright sprinkler head in the fourth floor attic system remote area. The new node point was 400. The north/south will is ok to cover. No inspection has been done on the east/west wing.
Sprinkler Plan Check3/31/2006 5/1/2006 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  5/1/2006 DONE
Permit Ready to Issue  5/1/2006 DONE
Inspection Record Card- Fire5/1/2006 5/1/2006 DONE
Telephone call  5/1/2006 DONE
Left voice message for Roger that permit is ready & fees @10:45am 5/1/06 BAS
Issue and Print Permit  5/1/2006 DONE
INSP-Sprinkler Rough-in4/26/20064/27/20064/27/2006APART
DetailsTroy Cobbley
Dry pipe system for the north wing has been inspected and passed for the most part. The areas of concern are: one sprinkler upright has been added in the remote area at the very north end which will require resubmittals and there is inadequate coverage above the elevator shaft.
INSP-Sprinkler Rough-in4/6/20064/7/20064/7/2006APASS
DetailsTroy Cobbley
The stand pipes have been converted to wet. but the riser still needs to be installed in its final configuration.
INSP-Supply line flush3/30/20063/31/20063/31/2006AFAIL
DetailsTroy Cobbley
Wrong permit number called in. See FIR05-00509 for entry.
INSP-Sprinkler Rough-in/Hydro3/30/20063/31/20063/31/2006AFAIL
DetailsTroy Cobbley
Wrong permit number called in. See FIR05-00509 for entry.
Plan resubmittals received  3/31/2006 DONE
Case Summary  3/31/2006 DONE
INSP-Sprinkler Rough-in3/15/20063/16/20063/16/2006APART
DetailsTroy Cobbley
The wet stand pipes have been installed as dry temporarily with dave hannimans approval. Signage with gpm and psi requirements have been placed at the fdc. The standpipes are to be converted to wet when the building is enclosed and heated. Work can now continue on the fourth floor and above.
Sprinkler Plan Check2/13/2006 3/9/2006 PART
DetailsBill Alexander
Re-Submittals Required On the Following:
1. Area #7 and 8 do not meet minimum requirements for NFPA 13 System Residential Sprinklers per NFPA 13-11.2.3.5.2* densities, (which is also addressed in the manufacturers head listing installation requirements). Revise, correct and resubmit. (IFC 105.4.2, 901.2 & BMC 7-01-50-IFC 901.2)

2. Standpipe - FP2 and 4 Plans and calculations need clarified.
a. Provide cuts and identify which standpipe is which in section cuts #2 and #3 on FP4.
b. Provide clarification how HV1, HV3 and HV4 are all at 47'-0"? What happened to the HV1 being on the roof which scales higher?
c. North stairs may go to the roof, but may not be the most demanding? Calculations are required to verify the most demanding which include elevation loss pressures.
Revise, clarify and resubmit. (IFC 105.4.2, 901.2 & BMC 7-01-50-IFC 901.2)

3. Area #9 FP2 plan hydraulic calculation "sticker" does not match the "Fire Sprinkler Hydraulic Calculation Cover Sheet" and calculations. Please correlate correct information. (IFC 105.4.2, 901.2 & BMC 7-01-50-IFC 901.2)
PLANS/APPL TAKEN TO FRONT DESK  3/9/2006 DONE
Inspection Record Card- Fire3/9/2006 3/9/2006 DONE
Telephone call  3/9/2006  
tlk to tom easton ###-#### that permit and fees are ready to be picked up
Permit Ready to Issue  3/9/2006 DONE
Issue and Print Permit  3/9/2006 DONE
Plan assigned to (Bill)9/30/2005 3/9/2006 DONE
Plan resubmittals received  2/13/2006  
Miscellaneous action  1/11/2006 DONE
Returned failed plans to permit desk for returning.
Telephone call  1/11/2006 DONE
lft vm with tom easton ###-#### that permit has failed and needs to be picked up
Sprinkler Plan Check12/16/2005 1/11/2006 FAIL
DetailsBill Alexander
The data has been moved to a Word document attached to this case.
Miscellaneous action  1/9/2006 DONE
Tom Easton request this review be stopped and put in place KOI Restaurant FIR05-00583.
Plan resubmittals received  12/19/2005 DONE
Sprinkler Plan Check11/4/2005 12/8/2005 FAIL
DetailsGay Runyon
By Troy
Plan resubmittals received  11/4/2005 DONE
Sprinkler Plan Check9/30/2005 10/19/2005 FAIL
DetailsBill Alexander
The data has been moved to a Word document attached to this case.
Telephone call  10/19/2005 DONE
called tom to verify plans failed return to sender
Application received  9/30/2005