Permit Information
Permit NumberFIR05-00648
StatusFinaled
Name IDAHO FIRE PROTECTION
Site Address 7960 W NORTHVIEW ST
Project NameSPR ST MARKS FOOD BANK
Customer Number 
ePlanReview 
Description
ST MARKS FOOD BANK ADDITION * To extend and existing fire sprinkler system in a new 1856-ft/2 one story, type V-B addition on the north side of existing building "A". This fire protection work shall comply with the IFC 2003 and the permit review comments; each regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD05-02014.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/6/20094/6/20094/6/2009PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection1/17/20061/17/20061/17/2006PPART
DetailsTroy Cobbley
A temporary occupancy was given until the fire alarm permit is approved. This permit needs finaled as well if correction have been made.
INSP-Sprinkler Rough-in/Hydro12/12/200512/12/200512/13/2005PPASS
DetailsTroy Cobbley
Sprinkler piping is ok to cover. Corrections made.
INSP-Sprinkler Rough-in/Hydro11/30/200512/1/200512/1/2005PFAIL
DetailsForrest France
Provide approved EQ attatchment methods for TJI's, upright coverage is blocked at area adjacent to restrooms by ductwork, sheetrock has been installed to full height where not shown, drop ceilings are not complete. The overhead hydro test passed inspection.
Issue and Print Permit  11/18/2005  
Sprinkler Plan Check11/17/2005 11/17/2005 PASS
Plans approved with coditions.
PLANS/APPL TAKEN TO FRONT DESK  11/17/2005 DONE
Permit Ready to Issue  11/17/2005 DONE
Inspection Record Card- Fire11/17/2005 11/17/2005 DONE
Telephone call  11/17/2005 DONE
left mess that permit is ready
Plan resubmittals received  10/27/2005 DONE
Issue permit  10/24/2005 DONE
Plan assigned to (Bill)10/3/2005 10/20/2005 DONE
Sprinkler Plan Check10/20/2005 10/20/2005 PART
DetailsBill Alexander
1. Plans and calculations do not correlate and plans are lacking. Designer shall read NFPA 13-14.1.3 and provide all that applies. Specifically paragraphs #6, 7, 18, 21, 22, 23, 28, 30, 31, 32, 38, 41, etc., etc.

2. Construction information is lacking (which includes reference in item #1 above with NFPA 13-14.1.3[38]). Read NFPA 13-9.3.2*, which includes requirements of 9.3.4* for "frangible" walls, etc. The other issue is wall and opening construction protection meeting requirements of NFPA 13:11.1.1, 11.2.3.1.1 Table 11.2.3.1.1 "Duration" (minutes) with corresponding hazard in 11.2.3.3.5. This must be reflected for all rooms. Designer shall verify and include system piping design incorporating minimum installation code requirements on the plans.

3. Provide information addressed and regarding NFPA 13-8.2.1 on the plan.

4. Plan design/engineering is incomplete. Attachments to the bottom of TJI's have attachment requirements and limits for "screws" and "coach screw rods" which will be addressed on the plans. 3/8" coach screw rods in joist flanges exceeding 1¾" width only. Penetration of 3/8" requires a ¼" pilot hole drilled ½" maximum off center for flanges that are >2" and ¼" flanges that are <2". The designer shall apply correct manufacturer installation instructions on the plans when attaching ferrous hardware and fasteners to a manufactured truss or joist. These structural supports are manufactured in accordance with "National Design Specifications for Wood Construction", and have published corresponding limits for attachments of each, for recognized ferrous hardware and fastener addressed in NFPA 13.

5. Occupancy use and plan information is lacking (also addressed in #1 above with NFPA 13-14.1.3[7]). The word "Storage" is found on the plan and shall be addressed by Commodity Classification relating to height and storage system proposed by the tenant. Reference IFC Section 2302 "High-Piled Combustible Storage" (definition), and NFPA 13 Table 12.1.10.1.1. Commodities classifications can be found both in NFPA 13 and the IFC.

6. Calculation design is flawed. Calculations provided (which were not completely verified under this review) show heads #101, 102, 106, 107, 109, 110, and 111 are all operating under the required minimum operating pressure and gpm/ft/2 for a spacing design of 120 ft/2 as indicated.

7. It would appear the pipe installing will be trapped? Read and apply NFPA 13-8.15.2.5 requirements on the plans.
PLANS/APPL TAKEN TO FRONT DESK  10/20/2005 DONE
Inspection Record Card- Fire10/20/2005 10/20/2005 DONE
Permit Ready to Issue  10/20/2005 DONE
Telephone call  10/20/2005 DONE
called ###-#### and told Tom that permit is ready
Case Summary  10/3/2005 DONE
Application received  10/3/2005