INSP-Final Inspection | 3/2/2006 | 3/2/2006 | 3/2/2006 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Final Inspection | 2/17/2006 | 2/17/2006 | 2/17/2006 | P | CANC |
Troy Cobbley
|
|
|
Unable to get elevator contractor to site for adjustments
|
INSP-Final Inspection | 2/15/2006 | 2/17/2006 | 2/17/2006 | A | FAIL |
Troy Cobbley
|
|
|
Need to test the smoke detector at the top of the shaft and the flashing hat is not working
|
INSP-Final Inspection | 2/14/2006 | 2/16/2006 | 2/15/2006 | A | FAIL |
Troy Cobbley
|
|
|
Need to verify signals, test elevator recall. A smoke detector and horn/strobe on the second floor are overspaced. Need to test the a/v's in the checking cashing tenant and the massage parlor.
|
CHANGE STATUS TO (ISS) | | | 12/2/2005 | | DONE |
|
|
|
no fee
|
Permit Ready to Issue | | | 11/29/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 11/29/2005 | | 11/29/2005 | | DONE |
|
|
|
|
Telephone call | | | 11/29/2005 | | DONE |
|
|
|
left mess that permit is ready
|
Alarm Plan Check | 11/28/2005 | | 11/28/2005 | | PASS |
Troy Cobbley
|
|
|
Plan modifications approved with comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/28/2005 | | DONE |
|
|
|
|
Plan resubmittals received | | | 11/16/2005 | | DONE |
|
|
|
|
INSP-Final Inspection | 10/17/2005 | 10/18/2005 | 10/18/2005 | A | PART |
Troy Cobbley
|
|
|
Fire alarm panel, duct smoke detectors in new area, one duct detector in existing area and a/v's in Micheals have been tested. No other items tested. The existing duct smoke detectors need proven that they function as installed or they will need relocated. New area of Micheals is ok to occupy with fire dept. permission.
|
INSP-Final Inspection | 10/17/2005 | 10/17/2005 | 10/17/2005 | P | FAIL |
Troy Cobbley
|
|
|
Tested the batteries and phone lines and one duct smoke detector in Michaels. Phone line programming had to be changed so it could be supervised and horns didn't work
|
INSP-Final Inspection | 10/14/2005 | 10/14/2005 | 10/14/2005 | P | FAIL |
Forrest France
|
|
|
Request for temp. is denied.
|
Plan assigned to (Mary) | 10/3/2005 | | 10/6/2005 | | DONE |
|
|
|
|
Alarm Plan Check | 10/6/2005 | | 10/6/2005 | | PASS |
Troy Cobbley
|
|
|
Plans approved with comments
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/6/2005 | | DONE |
Troy Cobbley
|
|
|
|
Inspection Record Card- Fire | 10/6/2005 | | 10/6/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 10/6/2005 | | DONE |
|
|
|
|
Telephone call | | | 10/6/2005 | | DONE |
|
|
|
left mess that permit is ready
|
Issue and Print Permit | | | 10/6/2005 | | DONE |
|
|
|
|
Case Summary | | | 10/3/2005 | | DONE |
|
|
|
|
Application received | | | 10/3/2005 | | |
|
|
|
|
Inspection Record Card- Fire | 10/6/2005 | | | | |
|
|
|
|