Permit NumberFIR05-00652
StatusFinaled
Name DEBEST FIRE PROTECTION
Site Address 2954 S VICTORY VIEW WAY
Project NameSPR ADT TENANT
Customer Number 
ePlanReview 
Description
(ADT) To construct a relocate and add fire sprinklers in a vacant shell space for a new 4,685-ft/2 office/warehouse tenant in an existing 32,340-ft/2 building. Fire sprinkler is related to new interior walls and new suspended (10'-0") ceilings, with a conference room, a break room, an office, a showroom and 2 restrooms. Wall separating these rooms from the "warehouse" shall extend to the roof with 1 hour minimum separation. This building is fully fire sprinklered for area increase. This fire protection work shall comply with the IFC 2003 and the permit review comments; each regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD05-02318.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/25/200510/26/200510/26/2005APASS
DetailsTroy Cobbley
Fire sprinkler finaled
INSP-Final Inspection10/24/200510/24/200510/24/2005PFAIL
DetailsTroy Cobbley
Sprinkler piping in the office area is ok to cover but there are two existing upright sprinklers in the warehouse area that are located under the skylights/smoke vents. Per the superintendant they are drop out sky lights. The upright heads will need to be relocated but shall not exceed the 196 sq. ft. spacing.
Issue permit  10/20/2005 DONE
Plan assigned to (Bill)10/3/2005 10/19/2005 DONE
Sprinkler Plan Check10/3/2005 10/19/2005 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  10/19/2005 DONE
Inspection Record Card- Fire10/19/2005 10/19/2005 DONE
Permit Ready to Issue  10/19/2005  
Application received  10/3/2005