INSP-Final Inspection | 1/5/2006 | 1/5/2006 | 1/5/2006 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Supply line flush | 11/14/2005 | 11/15/2005 | 11/15/2005 | A | PASS |
Troy Cobbley
|
|
|
flush passed
|
INSP-Sprinkler Rough-in/Hydro | 11/14/2005 | 11/14/2005 | 11/14/2005 | P | PART |
Troy Cobbley
|
|
|
Hydro test was supposedly witnessed by the general contractor with Sam Rogers approval. I will need test papers with signatures for fire dept. Underground flush scheduled for tomorrow.
|
Miscellaneous action | | | 11/14/2005 | | DONE |
|
|
|
I approved UG flush and hydro to be witnessed by GC, Perry w/ Benchmarch; he must sign the NFPA 13 Certificate; due to unavailibility of fire inspector to be present.
|
INSP-Supply line flush | 11/10/2005 | 11/10/2005 | 11/10/2005 | P | CANC |
Troy Cobbley
|
|
|
no time for inspection
|
INSP-Sprinkler Rough-in | 10/21/2005 | 10/21/2005 | 10/23/2005 | P | PASS |
Troy Cobbley
|
|
|
PIV valve installed. Stem still needs installed.
|
INSP-Sprinkler Rough-in | 10/13/2005 | 10/14/2005 | 10/14/2005 | A | FAIL |
Forrest France
|
|
|
The yard post indicator as shown on approved plans is not installed, the north/south run and first thrust block are okay to cover.
|
Issue and Print Permit | | | 10/7/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 10/6/2005 | | 10/6/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 10/6/2005 | | |
|
|
|
|
Telephone call | | | 10/6/2005 | | DONE |
|
|
|
left mess that permit is ready
|
Plan assigned to (Bill) | 10/4/2005 | | 10/5/2005 | | DONE |
|
|
|
|
Sprinkler Plan Check | 10/4/2005 | | 10/5/2005 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 10/5/2005 | | DONE |
|
|
|
|
Application received | | | 10/4/2005 | | |
|
|
|
|