INSP-Final Inspection | 1/13/2006 | 1/13/2006 | 1/13/2006 | P | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Final Inspection | 1/12/2006 | 1/12/2006 | 1/12/2006 | P | FAIL |
Troy Cobbley
|
|
|
The duct detectors in the basement are mounted incorrectly. The fresh air must come in after the sampling tubes. Provide signage at the manual pull stations per IFC 907.4.4. Repair all exit signs and emergency lights. One smoke detector on the first floor needs relocated to be centered between the two diffusers.
|
INSP-Final Inspection | 1/9/2006 | 1/10/2006 | 1/10/2006 | P | CANC |
Troy Cobbley
|
|
|
Per the electrician the mechanical systems are dismantled and non functional at this point. No inspection performed.
|
INSP-Final Inspection | 1/5/2006 | 1/6/2006 | 1/6/2006 | P | FAIL |
Troy Cobbley
|
|
|
Alarm system was not ready to test. I did a walk through and found one location in the basement where the spot detector for the fire/smoke damper activation exceeded 5' from the damper. They are going to relocate it.
|
Issue and Print Permit | | | 10/24/2005 | | DONE |
|
|
|
|
Plan assigned to (Mary) | 10/5/2005 | | 10/20/2005 | | DONE |
|
|
|
|
Alarm Plan Check | | | 10/20/2005 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|