Permit NumberFIR05-00671
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 1480 S KIMBALL WAY
Project NameSPR CENTURY 21
Customer Number 
ePlanReview 
Description
(CENTURY 21) To modify and existing Light Hazard shell system installed under FIR03-00184, for a new 12,368-ft/2 office tenant occupying the entire building. Fire sprinkler work related to construction of new steel stud and gyp board interior non-bearing partitions, and a new non-rated suspended ceiling with fixtures. This building is fully fire sprinklered for area. This fire protection work shall comply with the IFC 2003 and the permit review comments; each regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD05-01936.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/3/200511/4/200511/4/2005APASS
DetailsTroy Cobbley
Permit finaled.
Sprinkler Plan Check10/27/2005 11/3/2005 PASS
DetailsBill Alexander
Calculations provided addressing 22'-0" of pipe added friction loss for 3'-0" FlexHead system. (Complete evaluation verification was not provided).
Plan assigned to (Bill)10/27/2005 11/3/2005 DONE
PLANS/APPL TAKEN TO FRONT DESK  11/3/2005 DONE
Inspection Record Card- Fire11/3/2005 11/3/2005 DONE
Permit Ready to Issue  11/3/2005 DONE
CHANGE STATUS TO (ISS)  11/3/2005 DONE
(F) Reprint permit  11/3/2005 DONE
Plan resubmittals received  11/2/2005 DONE
Sprinkler Plan Check10/26/2005 10/31/2005 FAIL
Submittal provided on Flexhead is different that listing.
Miscellaneous action  10/31/2005 DONE
Sent email to Brad Bettcourt of failed submittal.
Plan resubmittals received  10/26/2005 DONE
INSP-Sprinkler Rough-in10/24/200510/25/200510/25/2005AFAIL
DetailsTroy Cobbley
Plans do not show the flex heads that have been used. No inspection done. Resubmit plans showing flexheads.
Inspection Record Card- Fire10/24/2005 10/24/2005 DONE
Telephone call  10/24/2005 DONE
left mess that permit is ready
Issue permit  10/24/2005 DONE
Permit Ready to Issue  10/24/2005 DONE
Plan assigned to (Bill)10/6/2005 10/21/2005 DONE
Sprinkler Plan Check10/6/2005 10/21/2005 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  10/21/2005 DONE
Application received  10/6/2005  