INSP-Final Inspection | 5/3/2006 | 5/4/2006 | 5/4/2006 | A | PASS |
Forrest France
|
|
|
Overhead fire sprinkler work is satisfactory, permit finaled.
|
INSP-Final Inspection | 4/26/2006 | 4/26/2006 | 4/26/2006 | P | FAIL |
Forrest France
|
|
|
Three new offices at the NE corner have been built which have caused sprinklers to be overspaced.
|
INSP-Final Inspection | 11/22/2005 | 11/22/2005 | 11/22/2005 | P | PART |
Forrest France
|
|
|
Fire sprinkler work is satisfactory, final pending shell sprinkler final approval.
|
INSP-Sprinkler Rough-in/Hydro | 11/16/2005 | 11/17/2005 | 11/17/2005 | A | PART |
Forrest France
|
|
|
Overhead hydrostatic test passed.
|
INSP-Final Inspection | 11/16/2005 | 11/17/2005 | 11/17/2005 | A | FAIL |
Forrest France
|
|
|
Ceiling tile and escutcheons must be installed and protective caps removed in ALL areas prior to final.
|
INSP-Sprinkler Rough-in/Hydro | 11/15/2005 | 11/16/2005 | 11/16/2005 | P | FAIL |
Forrest France
|
|
|
Hydrostatic test not completed due to leakage per contractor.
|
INSP-Final Inspection | 11/15/2005 | 11/16/2005 | 11/16/2005 | P | NR |
Forrest France
|
|
|
This permit is not ready for final at this time.
|
INSP-Sprinkler Rough-in | 11/15/2005 | 11/16/2005 | 11/16/2005 | P | FAIL |
Forrest France
|
|
|
One head is overspaced as circled on plans, one head is too close to a heat diffuser for the supplied temp rating, need canopies and tile and hydrostatic test pre final.
|
Override - Parcel Holds | | | 11/3/2005 | | |
|
|
|
|
Inspection Record Card- Fire | 11/3/2005 | | 11/3/2005 | | DONE |
|
|
|
|
Override - Parcel Holds | | | 11/3/2005 | | |
|
|
|
|
Permit Ready to Issue | | | 11/3/2005 | | |
|
|
|
|
Telephone call | | | 11/3/2005 | | DONE |
|
|
|
left mess that permit is ready
|
Override - Parcel Holds | | | 11/3/2005 | | |
|
|
|
|
Issue and Print Permit | | | 11/3/2005 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 10/7/2005 | | 11/2/2005 | | DONE |
|
|
|
|
Sprinkler Plan Check | 10/7/2005 | | 11/2/2005 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/2/2005 | | DONE |
|
|
|
|
Miscellaneous action | | | 10/27/2005 | | DONE |
|
|
|
Gave early start approval to Pete Conlin via his email request as quoted below:
"I need to request an early start permit on our new office at BoDo Building 7. I know Bill is slammed and I agree to modify any of our work if Bill finds some problems with the plans. Please call me if this is acceptable. Pete Conlon Director of Maintenance
Colliers International 475 South Capitol Blvd.Boise, Idaho 83702
E-Mail Pete.Conlon@Colliersidaho.net
Cell Phone ###-####"
Reply:
"This will be acceptable based on your stipulated commitment to correct any deficiencies noted in the permit plan review comments when issued."
Sam
|
Application received | | | 10/7/2005 | | |
|
|
|
|