Permit NumberFIR05-00681
StatusFinaled
Name DEBEST FIRE PROTECTION
Site Address 755 W FRONT ST Unit: 300
Project NameCOLLIERS INTERNATIONAL BODO 7
Customer Number 
ePlanReview 
Description
(COLLIERS INTERNATIONAL - BODO BLDG #7 - 3RD STORY) This building is fire sprinklered for fire area and to allow the multi-theater complex. To relocate and add for sprinklers for the construction of a 10,130-ft/2 office tenant space located on the 3rd story of "BODO Building #7". The building shell was constructed under permit BLD04-01324 and fire sprinklers installed under FIR05-00372 (uncompleted to date). Fire sprinkler work is related to 2 restrooms, new interior nonbearing walls and new suspended ceilings. All fire protection work shall comply with the IFC 2003 and the permit review comments; each regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD05-02358.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/3/20065/4/20065/4/2006APASS
DetailsForrest France
Overhead fire sprinkler work is satisfactory, permit finaled.
INSP-Final Inspection4/26/20064/26/20064/26/2006PFAIL
DetailsForrest France
Three new offices at the NE corner have been built which have caused sprinklers to be overspaced.
INSP-Final Inspection11/22/200511/22/200511/22/2005PPART
DetailsForrest France
Fire sprinkler work is satisfactory, final pending shell sprinkler final approval.
INSP-Sprinkler Rough-in/Hydro11/16/200511/17/200511/17/2005APART
DetailsForrest France
Overhead hydrostatic test passed.
INSP-Final Inspection11/16/200511/17/200511/17/2005AFAIL
DetailsForrest France
Ceiling tile and escutcheons must be installed and protective caps removed in ALL areas prior to final.
INSP-Sprinkler Rough-in/Hydro11/15/200511/16/200511/16/2005PFAIL
DetailsForrest France
Hydrostatic test not completed due to leakage per contractor.
INSP-Final Inspection11/15/200511/16/200511/16/2005PNR
DetailsForrest France
This permit is not ready for final at this time.
INSP-Sprinkler Rough-in11/15/200511/16/200511/16/2005PFAIL
DetailsForrest France
One head is overspaced as circled on plans, one head is too close to a heat diffuser for the supplied temp rating, need canopies and tile and hydrostatic test pre final.
Override - Parcel Holds  11/3/2005  
Inspection Record Card- Fire11/3/2005 11/3/2005 DONE
Override - Parcel Holds  11/3/2005  
Permit Ready to Issue  11/3/2005  
Telephone call  11/3/2005 DONE
left mess that permit is ready
Override - Parcel Holds  11/3/2005  
Issue and Print Permit  11/3/2005 DONE
Plan assigned to (Bill)10/7/2005 11/2/2005 DONE
Sprinkler Plan Check10/7/2005 11/2/2005 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  11/2/2005 DONE
Miscellaneous action  10/27/2005 DONE
Gave early start approval to Pete Conlin via his email request as quoted below:
"I need to request an early start permit on our new office at BoDo Building 7. I know Bill is slammed and I agree to modify any of our work if Bill finds some problems with the plans. Please call me if this is acceptable. Pete Conlon Director of Maintenance
Colliers International 475 South Capitol Blvd.Boise, Idaho 83702
E-Mail Pete.Conlon@Colliersidaho.net
Cell Phone ###-####"
Reply:
"This will be acceptable based on your stipulated commitment to correct any deficiencies noted in the permit plan review comments when issued."
Sam

Application received  10/7/2005