INSP-Final Inspection | 2/26/2007 | 2/26/2007 | 2/26/2007 | P | PASS |
Forrest France
|
|
|
Correction notice items have been completed and verified per field inspection completed by M.Timmerman. Fire Alarm Permit Finaled.
|
INSP-Final Inspection | 2/5/2007 | 2/5/2007 | 2/5/2007 | P | PART |
Forrest France
|
|
|
Final pending c/n items.
|
INSP-Alarm Testing | 2/2/2007 | 2/2/2007 | 2/2/2007 | P | PART |
Forrest France
|
|
|
Permit final pending 5 item c/n left on site and discussed with general contractor.
|
INSP-Alarm Testing | 1/5/2007 | 1/5/2007 | 1/5/2007 | P | PART |
Forrest France
|
|
|
Correction notice items from previous inspectons for guest rooms and common corridors on floors 6 thru 11 have been verified for completion with the exception of HC guest rooms visible notification appliance synchronization.
|
Override - Parcel Holds | | | 1/5/2007 | | |
|
|
|
Inspection isn't to do with the mechanical room or geothermal stuff
|
Override - People Holds | | | 1/5/2007 | | |
|
|
|
Nothing to do with Devcon's people hold
|
INSP-Alarm Testing | 1/4/2007 | 1/4/2007 | 1/4/2007 | P | PART |
Forrest France
|
|
|
Fire alarm testing completed for the 11th floor guest rooms and common corridors. Three HC accessible rooms have strobe notification devices which are not in synchronization. No testing performed for the elevator lobby, service room, nac panels, or floor control for sprinkler monitoring at this time.
|
Override - Parcel Holds | | | 1/4/2007 | | |
|
|
|
Inspection isn't to do with the mechanical room or geothermal stuff
|
Override - People Holds | | | 1/4/2007 | | |
|
|
|
Nothing to do with Devcon's people hold
|
INSP-Alarm Testing | 1/3/2007 | 1/3/2007 | 1/3/2007 | P | PART |
Forrest France
|
|
|
Inspection completed for the 10th floor guest rooms and common corridor. Strobe notification devices are not yet synchronized on general alarm, non-functional speaker in room 1019 repaired while on site. Guest rooms, manual pulls, SD's, fire dampers tested okay.
|
Override - Parcel Holds | | | 1/3/2007 | | |
|
|
|
This is not to do with the plan mod area per Rob.....
|
Override - Parcel Holds | | | 1/3/2007 | | |
|
|
|
This is not to do with the plan mod area per Rob.....
|
Override - People Holds | | | 1/3/2007 | | |
|
|
|
nothing to do with the hold on devcon
|
INSP-Alarm Testing | 1/2/2007 | 1/2/2007 | 1/2/2007 | P | FAIL |
Forrest France
|
|
|
Alarm testing for the 9th floor guest rooms and common corridors only completed today. Noted the strobes are not in sync at the HC rooms 911 and 910, also noted the a/v in the 910 restroom is functional on strobe only and did not reset, dampers at two locations did not operate, the SD's in the common corridor failed to initiate a general alarm condition.
|
Override - Parcel Holds | | | 1/2/2007 | | |
|
|
|
|
Override - Parcel Holds | | | 1/2/2007 | | |
|
|
|
|
INSP-Alarm Testing | 12/29/2006 | 12/29/2006 | 12/29/2006 | P | DEFR |
Forrest France
|
|
|
Rob ###-#### Note: 9th floor Not enough time available with todays schedule that an entire floor inspeciton could be completed. Inspection rescheduled for next week.
|
Override - Parcel Holds | | | 12/29/2006 | | |
|
|
|
|
Override - Parcel Holds | | | 12/29/2006 | | |
|
|
|
|
INSP-Alarm Testing | 12/27/2006 | 12/28/2006 | 12/28/2006 | P | PART |
Forrest France
|
|
|
8th floor FA testing performed today, noted the two HC accessible rooms (810 and 811) have non-functional strobe notification devices upon room smoke detection, door holders at the elevator lobby are not programmed, need visual inspection of dampers at two locations, the remainder of guest rooms and common corridor on this floor tested okay.
|
Override - Parcel Holds | | | 12/27/2006 | | |
|
|
|
|
Override - Parcel Holds | | | 12/27/2006 | | |
|
|
|
|
INSP-Alarm Testing | 12/19/2006 | 12/20/2006 | 12/21/2006 | A | PART |
Forrest France
|
|
|
Alarm tested satisfactory for the 6th floor guest rooms and common corridor areas. Sprinkler monitoring, elvator lobby, FJ remain to be tested on this floor. Also retested defficiencies on the 7th floor, the added SD in room 728 has not yet been programed, signage is to be provided at the visible "door chime" in the HC accessible room, noted voice evac in the guest rooms does not function on general alarm.
|
INSP-Final Inspection | 12/19/2006 | 12/19/2006 | 12/19/2006 | P | DEFR |
Forrest France
|
|
|
No time available to perform this inspection today, rescheduled as discussed with contractor.
|
Override - Parcel Holds | | | 12/19/2006 | | |
|
|
|
|
Override - Parcel Holds | | | 12/19/2006 | | |
|
|
|
|
INSP-Final Inspection | 12/13/2006 | 12/15/2006 | 12/15/2006 | A | CANC |
Forrest France
|
|
|
No time available to complete this inspection today.
|
Override - Parcel Holds | | | 12/13/2006 | | |
|
|
|
|
Override - Parcel Holds | | | 12/13/2006 | | |
|
|
|
|
INSP-Final Inspection | 12/6/2006 | 12/7/2006 | 12/7/2006 | A | FAIL |
Forrest France
|
|
|
Inspection conducted was for the 7th floor not including the sprinkler monitoring, FJ, and elevator recall. Noted three strobes in the main corridor with incorrect cd, SD in two rooms 728 and 730 are blocked by beams, the HC accessible room strobe notification device must function on general alarm, the "doorbell strobe" device violates IFC 2003 901.4.4.
|
Override - Parcel Holds | | | 12/6/2006 | | |
|
|
|
|
Override - Parcel Holds | | | 12/6/2006 | | |
|
|
|
|
INSP-Conference | 8/25/2006 | 8/28/2006 | 8/28/2006 | A | DONE |
Forrest France
|
|
|
On site confrence to discuss notification issues at select locations in the corridor, vending areas, and guest rooms per review comments. Noted a/v locations which may not meet min. code requirements for proper coverage and installation.
|
INSP-Alarm Testing | 8/11/2006 | 8/11/2006 | 8/11/2006 | P | NR |
Forrest France
|
|
|
Entry to document the observance of fire alarm wire installation for the hotel guest rooms without and prior to issuance of a FA permit and approved FA plans. Both the electrical contractor and general contractor have been notified that work is to cease until FA plans have been submitted and approved. Also notified contractors a stop work order will be issued Monday 8/14 unless a permit has been issued or pulled wire removed.
|
Miscellaneous action | | | 4/6/2006 | | DONE |
|
|
|
Dave Hanneman was given a roll plans while on site 4/4/06 to deliver to Mary Froemke. No cover sheet, permit number, or explanation of the plans was provided. The roll had one set of FA plans pertaining to the Hampton Inn levels of the hotel for which we have no existing fire alarm permit. The only FA permit we have is this one (FIR05-00695) which is limited to the parking levels. I called Devcon (James Woodbury) and TriState Electric (Max Stith) and left voice messages explaining our dilemma with this set of plans. I also explained that plan submittals require two sets of plans and a completed permit application cover sheet indicating the nature of the submittal (new, resubmittal, design alternative proposal, etc) and that if they want an alternate design approval, the plans need to be prepared and stamped by a licensed design professional and a cover letter provided by him explaining how the design alternative provides equivalent protection.
|
INSP-Final Inspection | 3/16/2006 | 3/16/2006 | 3/16/2006 | P | PART |
Forrest France
|
|
|
Fire alarm for the parking garage 1st, 2nd and 3rd levels ONLY tested acceptable for temporary occupancy request.
|
INSP-Final Inspection | 3/10/2006 | 3/13/2006 | 3/13/2006 | A | FAIL |
Forrest France
|
|
|
Third floor alarm pressure switch at the dry system failed to reset, low air at the ground level garage dry system adjusted while on site, signal verification list to be faxed in, requested date on batteries at panel. Tested third, second, ground level garage floors, stair 4 elevator, stair 4 and 3 alarm and notification devices, tested pump room, command center, and fire rated corridor alarm/notification/trouble and supervisory conditions, verified items on previous c/n have been completed for the generator room.
|
INSP-Alarm Testing | 3/9/2006 | 3/10/2006 | 3/10/2006 | A | CANC |
Forrest France
|
|
|
inspection scheduled to wrap up garage devices; Phone #: ###-#### Internet Inspection Request from: Terry Owsley Inspection cancelled from web by: Terry Owsley
|
INSP-Final Inspection | 3/2/2006 | 3/9/2006 | 3/9/2006 | A | FAIL |
Forrest France
|
|
|
Several monitoring points on the fire sprinkler system are not in condition to be tested including the dry systems (air compressors are not set), wet system flow (drain issues), standpipe tampers (closed for hydro test), need to provide proper SD coverage for the generator room as device is overspaced, provide visual notification in the generator room as the proper dB cannot be acheived, provide notification for the HC parking spot on ground level. No test of the elevator as access not available, FJ in stair 2 is not installed. Partial test only of the ground level alarm system today, plans will require resubmittals reflecting all changes, condition of the job prevents completion of testing for approval.
|
CHANGE STATUS TO (ISS) | | | 3/1/2006 | | |
|
|
|
Per Mary F. this is a partial issue//3/1/06 LEG
|
(F) Reprint permit | | | 3/1/2006 | | DONE |
|
|
|
|
Telephone call | | | 2/27/2006 | | DONE |
|
|
|
Requested matrix and battery calculations
|
Inspection Record Card- Fire | 2/27/2006 | | 2/27/2006 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 2/27/2006 | | DONE |
|
|
|
|
Plan resubmittals received | | | 2/27/2006 | | DONE |
|
|
|
Received matrix and battery calculations
|
Telephone call | | | 2/27/2006 | | DONE |
|
|
|
called ###-#### and told Rob that permit is ready for partial issue and fees
|
Alarm Plan Check | | | 2/26/2006 | | PART |
|
|
|
Plan Modification to remove all secondary water tank monitoring.
A resubmittal will be required when the secondary water tank design has been approved.
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/26/2006 | | DONE |
|
|
|
|
Plan resubmittals received | | | 2/24/2006 | | DONE |
|
|
|
|
Case Summary | | | 2/24/2006 | | |
|
|
|
|
Plan assigned to (Mary) | 10/13/2005 | | 11/30/2005 | | DONE |
|
|
|
|
Alarm Plan Check | | | 11/30/2005 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/30/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 11/30/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 11/30/2005 | | 11/30/2005 | | DONE |
|
|
|
|
Telephone call | | | 11/30/2005 | | DONE |
|
|
|
Left message for Rob that permit is ready & fees///11/30/05 @ 11:35am BAS
|
Issue and Print Permit | | | 11/30/2005 | | DONE |
|
|
|
|
Plan resubmittals received | | | 11/9/2005 | | DONE |
|
|
|
|
Alarm Plan Check | | | 11/7/2005 | | FAIL |
|
|
|
Resubmittal required. Faxed comments to Rob Ahten.
|
Plan resubmittals received | | | 11/2/2005 | | DONE |
|
|
|
|
Alarm Plan Check | | | 10/31/2005 | | FAIL |
|
|
|
No written comments. Resubmittal required.
|
Plan resubmittals received | | | 10/27/2005 | | DONE |
|
|
|
|
Alarm Plan Check | | | 10/25/2005 | | FAIL |
|
|
|
No written comments. Spoke with Rob Ahten, regarding the required monitoring of all sprinkler items. His plans do not match the sprinkler plans. I requested he discuss with DeBest and either give an explanation, or resubmit with the correct sprinkler monitoring items.
|
Alarm Plan Check | | | 10/24/2005 | | FAIL |
|
|
|
No written comments. Elevator #4 is a new item, motor in the pit. There are not the appropriate heats and smokes shown on the plans. Phoned Rob Ahten, Protex, stated a resubmittal is required.
|
Plan resubmittals received | | | 10/24/2005 | | DONE |
|
|
|
|
Plan resubmittals received | | | 10/20/2005 | | DONE |
|
|
|
|
Application received | | | 10/13/2005 | | |
|
|
|
|
Case Summary | | | 10/13/2005 | | DONE |
|
|
|
|