INSP-Final Inspection | 1/9/2007 | 1/9/2007 | 1/9/2007 | A | PASS |
Forrest France
|
|
|
C/N items have been verified for completion, final sprinkler inspection passed.
|
INSP-Sprinkler Rough-in/Hydro | 1/8/2007 | 1/8/2007 | 1/8/2007 | P | PART |
Forrest France
|
|
|
AG hydro passed, noted items missing for final including lack of a sufficient reliable heat source for the riser room, signage, head box, etc.
|
INSP-Supply line flush | 12/11/2006 | 12/12/2006 | 12/12/2006 | A | PART |
Forrest France
|
|
|
UG fire supply line flush completed.
|
INSP-Supply line flush | 12/4/2006 | 12/4/2006 | 12/4/2006 | P | PART |
Forrest France
|
|
|
UG fire supply line hydro passed.
|
INSP-Sprinkler Rough-in/Hydro | 5/1/2006 | 5/1/2006 | 5/2/2006 | P | PART |
Forrest France
|
|
|
Overhead rough-in is acceptable for cover at the 1st and 2nd floors only, need inspection for cold cavity protection at the 3rd floor prior to cover at this area.
|
Sprinkler Plan Check | 3/28/2006 | | 4/18/2006 | | PASS |
Bill Alexander
|
|
|
Revised calculcations due to major underground supply changes in underground permit FIR05-00787.
|
Miscellaneous action | | | 4/18/2006 | | DONE |
|
|
|
Took approved permit documents to permit desk for returning.
|
Issue permit | | | 11/14/2005 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 10/20/2005 | | 11/9/2005 | | DONE |
|
|
|
|
Sprinkler Plan Check | 10/20/2005 | | 11/9/2005 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/9/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 11/9/2005 | | 11/9/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 11/9/2005 | | |
|
|
|
|
Telephone call | | | 11/9/2005 | | DONE |
|
|
|
Called & left msg. for Tom permit ready to pick up on 11-9-05 @ 4:19 by BAS
|
Application received | | | 10/20/2005 | | |
|
|
|
|