Permit Information
Permit NumberFIR05-00708
StatusFinaled
Name IDAHO FIRE PROTECTION
Site Address 2903 W CANAL ST
Project NameSPR OH JEMS TRIPLEX BLDG #2
Customer Number 
ePlanReview 
Description
(JEMS PROPERTIES TRIPLEX BUILDING #2 - APT #101, 201, 301) To install a fire life safety NFPA 13R system to prevent flashover (total involvement) in the room of fire origin, where sprinklered, and to improve the chance for occupants to escape/evacuated required for building "story" increase per the 2000 IBC, in a new 3,375-ft/2 three story, triplex. This work does not include the underground supply. Separate permit required for fire service underground with multiple lead-in work. The first floor is two bedrooms and two baths, at 1,186-ft/2, the second floor is two bedrooms and two baths with a 1,186-ft/2 and the third floor is one bedroom and one bath with 816-ft/2. System shall be equipped with an alarm initiating device connected to an alarm system and an outside annunciating devise. All fire sprinkler work and related, which includes dual service underground water supply, the system backflow prevention device (provided by others), shall be per NFPA 13R, approved plans, engineering/red-lining and attached review comments, under direction of the Fire Chief. This permit is attached to: BLD05-00804.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/9/20071/9/20071/9/2007APASS
DetailsForrest France
Corrections are complete, final fire sprinkler inspection passed, permit finaled.
INSP-Sprinkler Rough-in/Hydro1/8/20071/8/20071/8/2007PPART
DetailsForrest France
OH hydro passed, noted missing bell sign, head box, signage at the riser room door, the main drain must be piped outside.
INSP-Supply line flush12/11/200612/12/200612/12/2006APART
DetailsForrest France
UG fire service supply line flush completed.
INSP-Supply line flush12/4/200612/4/200612/4/2006PPART
DetailsForrest France
UG supply line hydrostatic test passed.
INSP-Sprinkler Rough-in/Hydro7/12/20067/12/20067/12/2006APASS
DetailsTroy Cobbley
Tenting inspection passed. Sprinkler piping is ok to cover.
INSP-Sprinkler Rough-in/Hydro5/30/20065/30/20065/30/2006PPASS
DetailsTroy Cobbley
OK to cover.

Scheduled by a contractor via Hello! on 5/30/2006 at 4:56:40 AM. Contact: ###-####.
Sprinkler Plan Check3/28/2006 4/18/2006 PASS
DetailsBill Alexander
Revised calculations due to major underground supply changes in underground permit FIR05-00787.
Miscellaneous action  4/18/2006 DONE
Took approved permit documents to permit desk for returning.
Plan resubmittals received  3/28/2006 DONE
Issue permit  11/14/2005 DONE
Permit Ready to Issue  11/10/2005 DONE
Inspection Record Card- Fire11/10/2005 11/10/2005 DONE
Telephone call  11/10/2005 DONE
Left message for Tom that permit is ready & fees//11/10/05 9:20am BAS
Plan assigned to (Bill)10/20/2005 11/9/2005 DONE
Sprinkler Plan Check10/20/2005 11/9/2005 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  11/9/2005 DONE
Application received  10/20/2005