INSP-Final Inspection | 7/27/2006 | 7/27/2006 | 7/28/2006 | P | PASS |
Forrest France
|
|
|
Corrections have been completed, fire sprinkler permit finaled.
|
INSP-Final Inspection | 7/26/2006 | 7/26/2006 | 7/26/2006 | P | PART |
Forrest France
|
|
|
Forward flow test performed satisfactory, need to provide NFPA 25, noted one fitting is leaking above childrens restroom-to be repaired prior to final.
|
INSP-Final Inspection | 7/24/2006 | 7/24/2006 | 7/24/2006 | P | CANC |
Troy Cobbley
|
|
|
Scheduled by a contractor via Hello! on 7/24/2006 at 9:26:31 AM. Contact: ###-####.
|
INSP-Final Inspection | 7/17/2006 | 7/17/2006 | 7/18/2006 | P | PART |
Forrest France
|
|
|
Necessary corrections have been completed, final pending alarm testing at riser, forward flow.
|
INSP-Final Inspection | 7/11/2006 | 7/12/2006 | 7/13/2006 | A | CANC |
Troy Cobbley
|
|
|
roy; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|
INSP-Final Inspection | 7/10/2006 | 7/10/2006 | 7/10/2006 | P | PART |
Forrest France
|
|
|
Items on previous correction notice have been addressed, need to attatch unistrut hangers to structure with an approved method above two rooms at the west side, heads at west room are overspaced off one wall, verify heads in the skylights are the proper temp. rating, wall at the storage room east side will require sheetrock to maintain proper separation between upright heads.
|
INSP-Final Inspection | 6/29/2006 | 6/30/2006 | 6/30/2006 | P | FAIL |
Forrest France
|
|
|
Several items need correction, project is not ready for final inspection at this time. Preliminary rough-in inspection completed today addressing items such as incorrect hangers, spacing, head temps, seismic bracing and clearance, riser and plans which do not match installation- See 10 item correction notice left on site for review of a partial list of defficiencies. C/N does not constitute a complete listing of all issues regarding fire sprinklers at this time.
|
INSP-Sprinkler Rough-in/Hydro | 6/27/2006 | 6/28/2006 | 6/28/2006 | A | PART |
Forrest France
|
|
|
AG hydrostatic test completed.
|
INSP-Sprinkler Rough-in/Hydro | 6/26/2006 | 6/27/2006 | 6/27/2006 | A | FAIL |
Forrest France
|
|
|
AG hydro failed due to visible leakage at two locations not repaired from the previous inspection. UG hydrostatic test is satisfactory.
|
INSP-Sprinkler Rough-in/Hydro | 6/26/2006 | 6/26/2006 | 6/26/2006 | P | FAIL |
Forrest France
|
|
|
Visible leakage at three locations observed on the overhead system during hydrostatic test.
|
INSP-Supply line flush | 6/20/2006 | 6/21/2006 | 6/21/2006 | A | PART |
Forrest France
|
|
|
UG fire supply line flush performed satisfactory.
|
INSP-Sprinkler Rough-in | 6/16/2006 | 6/19/2006 | 6/19/2006 | A | PART |
Forrest France
|
|
|
UG supply line and riser are okay to cover, need to provide means for seismic clearance where ductile will pass through the floor slab.
|
CHANGE STATUS TO (ISS) | | | 5/4/2006 | | DONE |
|
|
|
per Sam Rogers ok to open permit.
|
Case Summary | | | 4/25/2006 | | |
|
|
|
|
Permit VOIDED | 4/21/2006 | 4/21/2006 | 4/21/2006 | | DONE |
|
|
|
THIS PERMIT HAS BEEN VOID TO CANCELLING PER COMMERICAL FIRE 4/21/2006
|
INSP-Conference | 3/13/2006 | 3/16/2006 | 3/16/2006 | P | CANC |
Forrest France
|
|
|
anita leatham; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ///cancelled per Anita w/Charlie Frog 3/16/06 10:06am LEG// Inspection cancelled from web by: Letitia Mesa
|
Issue permit | | | 11/15/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 11/14/2005 | | 11/14/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 11/14/2005 | | |
|
|
|
|
Telephone call | | | 11/14/2005 | | DONE |
|
|
|
left mess that permit is ready
|
Plan assigned to (Bill) | 10/21/2005 | | 11/11/2005 | | DONE |
|
|
|
|
Sprinkler Plan Check | 10/21/2005 | | 11/11/2005 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/11/2005 | | DONE |
|
|
|
|
Case Summary | | | 10/21/2005 | | DONE |
|
|
|
|
Application received | | | 10/21/2005 | | |
|
|
|
|