Information based on query as of Thursday, July 18, 2024.
Permit Information
Permit NumberFIR05-00719
StatusFinaled
Name DEBEST FIRE PROTECTION
Site Address 401 S 8TH ST
Project NameSPR MAGGIE MOO'S - 8TH ST
Customer Number 
ePlanReview 
Description
MAGGIE MOO'S * Additional and relocation of heads in an existing fire sprinklered building related to the remodel an existing 1,750-ft/2 tenant space (988 square feet for assembly and 762 square feet for the kitchen) for a new ice cream shop located on the 1st story of an existing 3 story, with basement, building. Fire sprinkler work is related to new interior nonbearing walls suspended ceilings and 265-ft/2 of floor structure to fill in a floor opening between the 1st story and the basement. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD05-002218.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/9/20065/9/20065/10/2006PPASS
DetailsForrest France
Fire sprinkler permit finaled.
INSP-Sprinkler Rough-in/Hydro5/5/20065/5/20065/5/2006PPASS
DetailsForrest France
Fire sprinkler corrections have been made, inspection passed.
INSP-Final Inspection5/4/20065/4/20065/4/2006PFAIL
DetailsForrest France
At the time of inspection (approx. 1:30 pm) the required corrections had not been made.
INSP-Final Inspection5/3/20065/4/20065/4/2006AFAIL
DetailsForrest France
Need to install ceiling tile and escutcheon at one location, install partition between wall and cooler as discussed, one head at the service counter does not match the temp. and response of the remainder of heads in the fire area.
INSP-Sprinkler Rough-in/Hydro4/25/20064/26/20064/26/2006APASS
DetailsTroy Cobbley
The sprinkler piping is ok to cover. Insulation had fallen on the upright sprinkler heads but was repaired as I waited.
Permit Ready to Issue  4/24/2006 DONE
Telephone call  4/24/2006  
tlk to receptionist that permit and fees are ready to be picked up
(F) Reprint permit  4/24/2006 DONE
CHANGE STATUS TO (ISS)  4/24/2006 DONE
issued previously
Sprinkler Plan Check4/3/2006 4/21/2006 PASS
DetailsBill Alexander
No written comments. IFC Fire/Life Safety to field verify.
Plan assigned to (Bill)4/3/2006 4/21/2006 DONE
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  4/21/2006 DONE
Plan resubmittals received  4/3/2006  
INSP-Sprinkler Rough-in/Hydro3/22/20063/23/20063/23/2006APART
DetailsTroy Cobbley
sprinkler piping in soffits is ok to cover. Plans need to be resubmitted to show this piping in the soffits. Pipe sizing has been increased to allow the heads but installation just does not match plans.
Issue permit  11/15/2005  
Plan assigned to (Bill)10/24/2005 11/14/2005 DONE
Sprinkler Plan Check11/14/2005 11/14/2005 PASS
Approved as noted. No written comments.
PLANS/APPL TAKEN TO FRONT DESK  11/14/2005 DONE
Permit Ready to Issue  11/14/2005 DONE
Inspection Record Card- Fire11/14/2005 11/14/2005 DONE
Telephone call  11/14/2005 DONE
Spoke with Randy and told him that permit is ready & fees///11/14/05 4:15PM BAS
Miscellaneous action  11/9/2005 DONE
Approved Early Start agreement per new guidelines; on file with B.A.
Application received  10/24/2005