INSP-Final Inspection | 9/21/2010 | 9/22/2010 | 9/23/2010 | A | PASS |
Troy Cobbley
|
|
|
permit finaled
|
FIR-Aging Inspection | 9/21/2010 | 9/21/2010 | 9/21/2010 | | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Sprinkler Rough-in | 7/12/2010 | 7/12/2010 | 7/12/2010 | P | PASS |
Troy Cobbley
|
|
|
permit finaled
|
INSP-Conference | 6/10/2010 | 7/1/2010 | 7/2/2010 | A | DONE |
Troy Cobbley
|
|
|
I left a message on Joan's voice mail at AIE ###-#### requesting job status.
|
INSP-Conference | 6/2/2010 | 6/10/2010 | 6/10/2010 | A | DONE |
Troy Cobbley
|
|
|
Per Joan the electrical work has been scheduled. She will call with a follow up status shortly.
|
INSP-Conference | 5/24/2010 | 6/2/2010 | 6/2/2010 | A | DONE |
Troy Cobbley
|
|
|
See todays entry for the final inspection for project status.
|
INSP-Final Inspection | 6/2/2010 | 6/2/2010 | 6/2/2010 | P | FAIL |
Troy Cobbley
|
|
|
When the system was tripped the appliances shut off but the lights under the hood did not shut off. Inspection was stopped. The hood suppression system did go to the fire alarm panel. I noted that the secondary phone line on the fire alarm panel was in a trouble condition. I notified Chad, the store manager that the phone line would need to be repaired as well as the lights shutting off under the hood. The manual pull station was not tested. No paper work was accepted. I also contacted Joan with AIE at ###-####.
|
INSP-Conference | 5/20/2010 | 5/24/2010 | 5/24/2010 | A | DONE |
Troy Cobbley
|
|
|
I spoke to Joan with AIE ###-#### and she was going to follow up with the installing contractor.
|
INSP-Conference | 5/12/2010 | 5/20/2010 | 5/20/2010 | A | CANC |
Troy Cobbley
|
|
|
Rescheduled for next monday.
|
FIR-Aging Inspection | 5/12/2010 | 5/12/2010 | 5/12/2010 | | NR |
Troy Cobbley
|
|
|
Contractor is following up on the alarm interconnection. A follow up inspection has been scheduled for next week.
|
INSP-Final Inspection | 10/26/2005 | 11/8/2005 | 11/8/2005 | A | FAIL |
Troy Cobbley
|
|
|
No test was performed due to lights not turning off under the hood and the suppression system not being connected to the fire alarm system.
|
Issue and Print Permit | | | 10/26/2005 | | DONE |
|
|
|
|
Application received | | | 10/25/2005 | | |
|
|
|
|
Permit Ready to Issue | | | 10/25/2005 | | DONE |
|
|
|
|