Information based on query as of Saturday, August 17, 2024.
Permit Information
Permit NumberFIR05-00735
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 917 S LUSK ST Unit: 300
Project Namealm - KEYNETICS
Customer Number 
ePlanReview 
Description
Fire alarm permit FIR05-00169 (shell and core) must be completed (finaled) prior to occupancy for permit (FIR05-00735).

Fire alarm permit FIR05-00169 (shell and core) and FIR05-00715 (pre-action releasing system) must be completed (finaled) prior to occupancy for permit (FIR05-00734).

To provide total notification, fire/smoke damper control and HVAC shutdown to an existing required manual fire alarm system which includes, manual fire boxes, HVAC shutdown, fire/smoke damper control, elevator recall/shutdown and total notification throughout.

FIR05-00715 is a pre-action releasing system (panel located in the electrical room, first floor) that will supply an IT room on the second floor and the electrical room (first floor directly below the IT room) that feeds the IT room. The FACP shall monitor the pre-action control panel for alarm, supervisory and trouble signals.

FIR05-00734 is associated with building permit BLD05-01478 is to occupy the entire second floor in existing vacant shell building per approved plans. Work under this permit will also include constructing a building core corridor with lobby, exercise room with showers, pantry, mail room, and janitor's closet on the first floor of the building. Work to include new interior walls, new interior doors, some new interior glazing, interior finish, new suspended ceiling installation, new soffit work, new cabinets/counters and sinks, fire sprinkler and fire alarm work, new mechanical, new plumbing, and new electrical work. A Certificate of Occupancy is to be issued when completed and approved. NOTE: This building is fully fire sprinklered for story increase and area increase. JCB (CLICKSALES)(KEYNETICS BLDG - 2ND FLOOR) New 7,628 sq. ft. office tenant

FIR05-00735 is associated with building permit BLD05-01480 is to occupy the entire third floor in existing vacant shell building per approved plans. Work to include new interior walls, new interior doors, some new interior glazing, interior finish, new suspended ceiling installation, new soffit work, new cabinets/counters and sinks, fire sprinkler and fire alarm work, new mechanical, new plumbing, and new electrical work. A Certificate of Occupancy is to be issued when completed and approved. NOTE: This building is fully fire sprinklered for story increase and area increase. JCB (KEYNETICS)(KEYNETICS BLDG - 3RD FLOOR) New 7,967 sq. ft. office tenant

Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/19/200512/20/200512/20/2005ADONE
DetailsForrest France
This inspection already completed, wrong permit number requested by contractor.
INSP-Final Inspection12/16/200512/19/200512/19/2005PPASS
DetailsForrest France
Fire alarm passed inspection for the third floor TI space.
INSP-Final Inspection12/14/200512/15/200512/15/2005PFAIL
DetailsForrest France
The lens on wall mounted strobes at each device in the TI area are mounted too low, not meeting min. code requirements.
Plan assigned to (Mary)10/28/2005 11/30/2005 DONE
Alarm Plan Check  11/30/2005 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  11/30/2005 DONE
Inspection Record Card- Fire11/30/2005 11/30/2005 DONE
Permit Ready to Issue  11/30/2005  
Issue and Print Permit  11/30/2005 DONE
Plan resubmittals received  11/14/2005 DONE
Case Summary  11/14/2005 DONE
Case Summary  10/28/2005 DONE
Case Summary  10/28/2005 DONE
Application received  10/28/2005