Case Summary | | | 10/23/2012 | | DONE |
|
|
|
|
INSP-Final Inspection | 1/29/2007 | 1/30/2007 | 1/31/2007 | P | PASS |
Forrest France
|
|
|
Retest of the fire alarm system passed inspection, permit finaled.
|
INSP-Final Inspection | 1/25/2007 | 1/29/2007 | 1/29/2007 | P | DEFR |
Forrest France
|
|
|
Inspection rescheduled.
|
INSP-Final Inspection | 11/1/2006 | 11/1/2006 | 11/1/2006 | P | FAIL |
Forrest France
|
|
|
Missing heat and smoke detectors at the top of the elevator shaft, one duct detector has the wrong sample tube installed, one duct detector is not properly located downstream of all returns, damper above the door to the mech. room is not functioning, tested FACP batteries, phone lines, AC loss, and panel smoke, signals not verified at this time, concluded inspection due to the number of defficiencies, no other items tested.
|
FIR-Aging Inspection | 8/30/2006 | 8/30/2006 | 9/6/2006 | | DONE |
Forrest France
|
|
|
On site visit to determine status of work which is still in progress.
|
Issue and Print Permit | | | 2/9/2006 | | DONE |
|
|
|
|
Alarm Plan Check | | | 2/7/2006 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 2/7/2006 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 2/7/2006 | | 2/7/2006 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 2/7/2006 | | DONE |
|
|
|
|
Telephone call | | | 2/7/2006 | | DONE |
|
|
|
left mess that permit is ready
|
Plan resubmittals received | | | 1/9/2006 | | DONE |
|
|
|
|
Alarm Plan Check | | | 11/10/2005 | | FAIL |
|
|
|
Resubmittal required. Faxed comments to Charlie Bayne.
|
Application received | | | 10/31/2005 | | |
|
|
|
|
Plan assigned to (Mary) | 10/31/2005 | | | | |
|
|
|
|