Permit Information
Permit NumberFIR05-00745
StatusFinaled
Name AIC SOLUTIONS INC
Site Address 3615 S FEDERAL WAY
Project Namealm FAM CENTER-Bed Bath Beyond
Customer Number 
ePlanReview 
Description
To provide a required manual fire alarm system. The required manual fire alarm system includes sprinkler monitoring, HVAC shutdown and notification throughout.

The associated building permit (BLD 05-01209) is to construct a new 28,000 square foot, one story with 930 sq. ft. mezzanine, masonry and steel framed retail store and related site improvements. This building will infill between the existing Home Depot and Fred Meyers retail stores. This building is fully fire sprinklered and the sprinklers are used for unlimited area. All three retail stores are being considered one building for the purpose of determining allowable area. All construction per the approved plans and attached comment list. DRH05-00032/JCM Bed Bath & Beyond Retail Store -
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/7/200512/8/200512/8/2005APASS
DetailsForrest France
Defficiencies have been corrected, fire alarm passed inspection.
INSP-Final Inspection12/7/200512/7/200512/7/2005PFAIL
DetailsForrest France
Unable to test RTU 4 and 6 (were not operable), some av's are below 80" to the lens in the office area, need signal verification, inspection to be rescheduled for final.
Alarm Plan Check  12/7/2005 PASS
Plan Modification. Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  12/7/2005 DONE
Inspection Record Card- Fire12/7/2005 12/7/2005 DONE
CHANGE STATUS TO (ISS)  12/7/2005 DONE
(F) Reprint permit  12/7/2005 DONE
Plan resubmittals received  12/7/2005 DONE
Received new plans and riser.
Plan resubmittals received  12/6/2005 DONE
Alarm Plan Check  12/6/2005 FAIL
New NAC Circuit added to FACP to cover storage area on east side of building. FACP capacity is 6.0A NAC, the design indicates 6.5A. Therefore I called Brian Richard, AIC explained the situation and stated that I would allow them to "insert" the modifications they needed into the existing submittal.
Inspection Record Card- Fire12/5/2005 12/5/2005 DONE
Telephone call  12/5/2005 DONE
left message with Dot that permit is ready & o fees due///12/05/05 @12:45pm BAS
Issue and Print Permit  12/5/2005 DONE
Plan assigned to (Mary)11/1/2005 12/5/2005 DONE
Alarm Plan Check  12/5/2005 PART
A resubmittal will be required prior to final inspection.

Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  12/5/2005 DONE
Permit Ready to Issue  12/5/2005 DONE
Miscellaneous action  12/2/2005 DONE
Approved early start request to install remainder of FA devices, including notification appliances and pull stations. We previously approved installation of FACP and fire sprinkler monitoring devices. The committed to make any modifications required per plan review at their expense. We expect plan review to be completed and permit issued on Monday, 12/5.
Alarm Plan Check  11/15/2005 FAIL
Resubmittal requried. Faxed comments to Samuel Flores.
Application received  11/1/2005  
Case Summary  11/1/2005 DONE
Inspection Record Card- Fire12/5/2005