INSP-Final Inspection | 1/27/2006 | 1/27/2006 | 1/27/2006 | P | PASS |
Forrest France
|
|
|
Fire sprinkler work is satisfactory, c/n items have been completed, permit finaled.
|
INSP-Sprinkler Rough-in/Hydro | 1/27/2006 | 1/27/2006 | 1/27/2006 | A | PART |
Forrest France
|
|
|
Hydrostatic test of the antifreeze system passed inspection, leakage has been repaired.
|
INSP-Final Inspection | 1/19/2006 | 1/20/2006 | 1/20/2006 | A | PART |
Forrest France
|
|
|
CORRECTIONS REQUIRED:
1. Alarm related devises need verified, tested and activated prior to ACCEPTANCE (this portion is connected to the new alarm system). This means FIR05-00712 needs finaled FIRST.
2. Anti-freeze riser needs flexible coupling at base and top of riser.
3. The anti-freeze riser needs tagged with an approved state Fire Marshal tag AND all antifreeze control valves, drains and auxiliary drains shall be provided with signage per NFPA 13-6.7.4*. Include hydraulic calculations sign for each design area per NFPA 13-16.5*. In addition, provide a tag indicating the type of solution, quantity, freeze point (indicate by what method tested), date installed and company.
4. Provide a lateral sway brace on the north end main of the Porte-Cohere (canopy).
5. Hydro test anti-freeze system.
|
INSP-Sprinkler Rough-in/Hydro | 12/19/2005 | 12/19/2005 | 12/19/2005 | P | CANC |
Forrest France
|
|
|
Wrong permit called in, the inspection under the correct related permit to be performed tomorrow as agreed.
|
Permit Ready to Issue | | | 12/1/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 12/1/2005 | | 12/1/2005 | | DONE |
|
|
|
|
Telephone call | | | 12/1/2005 | | DONE |
|
|
|
left mess that permit is ready
|
Issue and Print Permit | | | 12/1/2005 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 11/3/2005 | | 11/30/2005 | | DONE |
|
|
|
|
Sprinkler Plan Check | 11/30/2005 | | 11/30/2005 | | PASS |
|
|
|
Plans approved with comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/30/2005 | | DONE |
|
|
|
|
Case Summary | | | 11/3/2005 | | DONE |
|
|
|
|
Application received | | | 11/3/2005 | | |
|
|
|
|