Information based on query as of Thursday, July 18, 2024.
Permit Information
Permit NumberFIR05-00764
StatusFinaled
Name MOUNTAIN ALARM
Site Address 709 E RIVERPARK LN
Project Namealm - River Run Center
Customer Number 
ePlanReview 
Description
To provide a voluntary manual fire alarm system. The manual fire alarm system includes HVAC shutdown and notification throughout.

There is no associated building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/28/20066/29/20066/29/2006APASS
DetailsForrest France
Required corrections have been completed, final alarm inspection passed.
INSP-Final Inspection6/15/20066/16/20066/16/2006ACANC
DetailsForrest France
Per phone call from contractor, inspection to be rescheduled due to jobsite conditions.
INSP-Final Inspection6/7/20066/8/20066/8/2006AFAIL
DetailsForrest France
Manual pull stations at several locations are installed above max. height allowed, one H/S is overspaced in the open office area, remote indicator for the duct detector in the computer room is non-functional, fire alarm wire at some locations is incorrectly attatched, need to test one duct detector above a confrence room. FACP, nac panel, batteries, phone lines tested okay. Still need to test a/v's, manual pulls, dB, verify signals, etc.
Issue and Print Permit  12/13/2005 DONE
Permit Ready to Issue  11/22/2005 DONE
Inspection Record Card- Fire11/22/2005 11/22/2005 DONE
Telephone call  11/22/2005 DONE
Left voice message for Lynda that permit is ready & fees///11/22/05 @8:40am BAS
Plan assigned to (Mary)11/4/2005 11/21/2005 DONE
Alarm Plan Check  11/21/2005 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  11/21/2005 DONE
Application received  11/4/2005  
Case Summary  11/4/2005 DONE