INSP-Final Inspection | 12/30/2005 | 12/30/2005 | 12/30/2005 | P | PASS |
Troy Cobbley
|
|
|
permit finaled
|
Permit Ready to Issue | | | 12/16/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 12/16/2005 | | 12/16/2005 | | DONE |
|
|
|
|
Telephone call | | | 12/16/2005 | | DONE |
|
|
|
left mess that permit is ready
|
Issue and Print Permit | | | 12/16/2005 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 12/14/2005 | | 12/15/2005 | | DONE |
|
|
|
|
Sprinkler Plan Check | 12/14/2005 | | 12/15/2005 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/15/2005 | | DONE |
|
|
|
|
Plan resubmittals received | | | 12/14/2005 | | DONE |
|
|
|
|
Case Summary | | | 12/14/2005 | | DONE |
|
|
|
|
Issue and Print Permit | | | 12/8/2005 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 11/10/2005 | | 12/7/2005 | | DONE |
|
|
|
|
Sprinkler Plan Check | 11/10/2005 | | 12/7/2005 | | PART |
Bill Alexander
|
|
|
1. Shell system was not verified for 196-ft/2 spacing and this submittal does not verify the same. Either resubmit verification of system meeting area density spacing of 196-ft/2 or drop the sprinkler spacing to 148-ft/2 minimum through this tenant. This will also include the "Small Room Rule." (BMC 7-01-50:901.2, IFC 105.4.2, NFPA 13:4.3)
2. It would appear the Reception and Assist Room heads are blocked by soffits. Reference NFPA 13-Figure 8.6.5.1.29(a) and (b) for clarification and provide proof of meeting these requirements through resubmittals. (BMC 7-01-50:901.2, IFC 105.4.2, NFPA 13:4.3)
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/7/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 12/7/2005 | | 12/7/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 12/7/2005 | | DONE |
|
|
|
|
Telephone call | | | 12/7/2005 | | DONE |
|
|
|
left mess that permit is ready
|
Application received | | | 11/10/2005 | | |
|
|
|
|