Permit Information
Permit NumberFIR05-00787
StatusFinaled
Name IDAHO FIRE PROTECTION
Site Address 2903 W CANAL ST
Project NameSPR UG JEMS TRIPLEX BLDG
Customer Number 
ePlanReview 
Description
(JEMS PROPERTIES TRIPLEX BUILDING UNDERGROUND)
Building #2: To install 328'-0" of 2½" (transitioned to 2½"by United Water at a service valve) connected to (unspecified water service main) in Canal St., running south through the parking/driveway and 6'-6" of 2" CPVC into the fire sprinkler service riser room for an NFPA 13R system.
Building #3: To install 250'-0" of 2½" (transitioned to 2½"by United Water at a service valve) connected to (unspecified water service main) in Canal St., running south through the parking/driveway and 6'-6" of 2" CPVC into the fire sprinkler service riser room for an NFPA 13R system.
Building #4: To install 172'-0" of 2½" (transitioned to 2½"by United Water at a service valve) connected to (unspecified water service main) in Canal St., running south through the parking/driveway and 6'-6" of 2" CPVC into the fire sprinkler service riser room for an NFPA 13R system.
Building #5: To install 94'-0" of 2½" (transitioned to 2½"by United Water at a service valve) connected to (unspecified water service main) in Canal St., running south through the parking/driveway and 6'-6" of 2" CPVC into the fire sprinkler service riser room for an NFPA 13R system.
This permit is associated with underground work for: BLD05-00804, BLD05-00805, BLD05-00806, and BLD05-00807. Each underground lead-in supply will include separate repair gates for each of the 4 buildings sprinklered, for possible future individual lead-in repair separation. The fire sprinkler underground work shall comply with NFPA 13-2002, NFPA 24-2002 the IFC-2003, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum fire code.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/26/20103/26/20103/26/2010PPASS
DetailsForrest France
Underground fire supply line permit final approved.
INSP-Conference3/26/20103/26/20103/26/2010PDONE
DetailsForrest France
Regarding permit status and conditions on parcel hold for this address.
Miscellaneous action  3/12/2010 DONE
Sent email requesting project status.
INSP-Supply line flush12/12/200612/12/200612/13/2006PPART
DetailsForrest France
UG supply line flush completed satisfactory.
INSP-Supply line flush5/16/20065/17/20065/17/2006APART
DetailsForrest France
UG fire supply lines are good for cover, will need to provide means for seismic clearance where the riser pipe passes through the floor slab, pipe is required to be bedded before backfill.
CHANGE STATUS TO (ISS)  4/20/2006  
no fee plans picked up
(F) Reprint permit  4/20/2006  
Sprinkler Plan Check3/28/2006 4/18/2006 DONE
DetailsBill Alexander
Inspection Record Card- Fire4/18/2006 4/18/2006 DONE
Telephone call  4/18/2006 DONE
lft vm with tom dutkus ###-#### that permit is ready to be picked up and no fees
Plan resubmittals received  3/28/2006  
Issue and Print Permit  1/20/2006 DONE
Plan assigned to (Bill)11/15/2005 12/12/2005  
Sprinkler Plan Check11/15/2005 12/12/2005 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  12/12/2005 DONE
Inspection Record Card- Fire12/12/2005 12/12/2005 DONE
Permit Ready to Issue  12/12/2005 DONE
Telephone call  12/12/2005 DONE
called ###-#### and left message that permit is ready and fees
Case Summary  11/15/2005  
Application received  11/15/2005