Permit Information
Permit NumberFIR05-00799
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 1055 N CURTIS RD
Project NamealmSARMC-FAMILY MATERNITY CNTR
Customer Number 
ePlanReview 
Description
To provide a required manual fire alarm system that includes required automatic detection, sprinkler monitoring, HVAC shutdown, fire/smoke damper control, door release, elevator recall/shutdown and notification throughout.

The associated building permit (BLD 05-01063) is to finish the exterior & interior of a 38,020 square foot, two story addition with mechanical penthouse, adjacent to and connected to the existing Labor & Delivery Unit by two connecting links; to create patient rooms, exam rooms, nursing stations, administrative support and Neonatal Intensive Care Unit on the second floor; installation of millwork, electrical, plumbing, mechanical, electrical, fire suppression, alarm and medical gas as per tenant needs and compliance with codes and ordinances; to install a suspended ceiling grid system and interior finishes; to remodel a portion of the existing FMC for sleeping rooms for medical personnel; and to install exterior glazing and finishes. (drs) (ST ALPHONSUS)(FAMILY MATERNITY CENTER EXPANSION/RENOVATION)
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/22/20071/22/20071/22/2007PPASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection1/11/20071/11/20071/11/2007PFAIL
DetailsTroy Cobbley
All of the strobes are mounted too low. No testing performed.
(F) Reprint permit  11/8/2006 DONE
Inspection Record Card- Fire11/7/2006 11/7/2006 DONE
Telephone call  11/7/2006  
t/c w Charlie Bayne at ###-####- permit ready and no fees (phase one)
Miscellaneous action  11/7/2006  
Conducted Phase One Fire Alarm System As-Built Review. The phase one fire alarm system scope of work on this project has been accepted by the field inspector. A Phase One temoprary occupancy has been issued. As-Built drawings reflecting changes made durring the project
INSP-Final Inspection9/15/20069/15/20069/15/2006PPART
DetailsTroy Cobbley
A temporary occupancy was given until the phase II (remodeled existing area) is complete. The new FMC building is complete.
INSP-Alarm Testing9/13/20069/13/20069/13/2006AFAIL
DetailsTroy Cobbley
The a/v's need to be exchanged in the ICU area and the nomanclature needs to be changed at the riser room devices as discussed. All other items on the correction notice have been corrected.
Miscellaneous action  9/13/2006 DONE
Received fax dated 9/1/06 from McCarthy indicating the WANdoor is not smoke rated, therefore smoke detector activation of the door is not required. However, Dan Stuart, plan reviewer determined that the door requires a smoke acitvated closer per IFC 1008.1.3.3 and the ES Listing report ER-3890, copy attached to approved plans. This responds to comment #1 on the 8/10/06 fire alarm modification plan review.
INSP-Alarm Testing9/5/20069/6/20069/6/2006ADONE
DetailsTroy Cobbley
See the city approved plans for devices tested today which included the induct detectors and duct detectors for unit shutdown. Per the mechanical contractor the max cfm in the trunk lines is roughly 1200. The simplex detectors are listed to 2000cfm.
INSP-Alarm Testing8/30/20068/31/20068/31/2006PDONE
DetailsTroy Cobbley
See city approved plans for locations of devices tested and problems found. This was only a partial test.
Issue and Print Permit  8/16/2006  
PLANS/APPL TAKEN TO FRONT DESK  8/15/2006 DONE
Permit Ready to Issue  8/15/2006 DONE
Telephone call  8/15/2006 DONE
left vm for charlie@###-####/told permit was ready, permit#, project name & address, and fee
Alarm Plan Check8/3/2006 8/10/2006 PASS
Plan modification - 8/3/06 mailed to F. Varley. 8/10/06 - Approved by F. Varley. Plans previously approved and sent back in after the engineers made changes to locations of some devices. No cut sheets were provided. I re-approved it with a few comments as additions to the original review. It is the third time the plans have been through the system; $150 review fee applies.
Plan resubmittals received  7/31/2006  
FIR-Aging Inspection6/28/20066/28/20066/29/2006 NR
DetailsTroy Cobbley
work is in progress
CHANGE STATUS TO (ISS)  3/29/2006 DONE
fees were not put in permit when customer was picking up this is why is changed the status to issued....i put fees in & billed them
Issue permit  3/29/2006 DONE
Issue and Print Permit  3/29/2006 DONE
Inspection Record Card- Fire3/27/2006 3/27/2006 DONE
Permit Ready to Issue  3/27/2006 DONE
Telephone call  3/27/2006  
lft vm with charlie ###-#### that permit and fees are ready to be picked up
PLANS/APPL TAKEN TO FRONT DESK  3/25/2006 DONE
Plan assigned to (Mary)11/22/2005 3/25/2006 DONE
Alarm Plan Check  3/24/2006 PASS
Approved pending field inspection of fire alarm permit comments.
Plan resubmittals received  3/10/2006 DONE
Alarm Plan Check  3/4/2006 FAIL
Resubmittal required. Faxed comments to Charlie Bayne.
Plan resubmittals received  2/17/2006  
Alarm Plan Check  12/7/2005 FAIL
No written comments. I marked up the drawings and called Charlie Bayne (Simplex) to let him know the plans have been rejected. His comments will consist of Charlie marking up his own set of drawings.
Application received  11/22/2005  
Case Summary  11/22/2005 DONE