Permit Information
Permit NumberFIR05-00801
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 1055 N CURTIS RD
Project Namealm St Al's Central Tower Add
Customer Number 
ePlanReview 
Description
This fire alarm permit is to provide the FCC (for the Central Tower, per IFC 509; obviously not all items will be completed in this permit, but will be required under another FA permit) to be located in the North tower. The generators for the Central Tower are to be installed and functional to supply emergency power to the Family Maternity Center (FMC). The basement areas required in the Central tower will be Comm (07201), Electrical rms (07202 & 07203) and the generator room, all located in the northwest portion of the basement in the Central Tower. As this will be a high-rise, voice-evac and fire department communication systems are required. At this point, the required manual fire alarm system includes fire pump monitoring, fire water tank monitoring, total area smoke detectors and notification throughout the above listed spaces.

The associated fire sprinkler permit (FIR 05-00536) is to 8" U.G. fire service supply, Fire Booster Pump, Secondary Water Tank System, Standpipes, Basement, through the 10th floors w/floor zone controls. The North Tower Remodels of the Basement, 1st, 2nd & 3rd, 4th Floor & South Tower Remodels 1st & 2nd Floors.

The associated building permit (BLD 05-00633) is to complete the interior build out & finish for portions of the entire 357,555 sq. ft., 10 story central tower, 9 stories for medical and support uses' and 1 story for mechanical penthouse and a 41,610 sq. ft. basement. First floor pharmacy and 2nd floor access corridor are being completed and occupied under separate permits (BLD05-00635 & BLD05-00634). Work includes protection of building elements per Table 601 for "IA" construction of 2003 IBC; framing to be non-combustible, with finishes per approved plans; electrical, plumbing, mechanical, fire suppression, alarm, medical gas and exit systems to meet tenant needs and provide compliance with minimum current adopted codes and ordinances. work also includes selective interior demolition and remodel of portions of the existing North and South Towers as they are connected to the new Central Tower. (drs) (ST ALPHONSUS CENTRAL TOWER)(INTERIOR FIT UP)
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/6/20086/9/20086/10/2008APASS
DetailsTroy Cobbley
permit finaled
Telephone call  8/16/2007 DONE
The following email was sent to Jeff Cramer, arch.
Jeff,
It is correct that any alarm installation work is required by Code to comply with NFPA 72 installation rules. As to your comment that they are not required, I will have to have the fire inspector evaluate each space according to IFC 907.2.12.1 (1) before we can confirm whether they are required or not. The Mechanical and Building inspectors (Alan Hauser and Tom Arcoraci) should also be in agreement before a final decision is made to remove them.
Regards,
Sam
Case Summary  6/14/2007 DONE
(F) Reprint permit  1/19/2007 DONE
Alarm Plan Check1/18/2007 1/18/2007 PASS
As Built Review Only: Conducted a (As-Built) review consisting of additional fire alarm notification devices, relocations of mechanical induct smoke detectors and the revised system riser for the Saint Alphonsus Central Tower Pharmacy. Review included clouded areas on the submitted As-Built floor plans only and verification that new devices were added to the system riser. All other areas of the floor plans are to be considered to have been previously reviewed and accepted by field inspection and former plan reviewer. No data sheets or revised battery calculations were provided. The number of initiating devices (2) added as shown should have little if any effect on the battery calculations. It is assumed that the end of line voltage was field inspected for additional notification circuits and is acceptable. No written comments are made to this review.
Telephone call  1/18/2007 DONE
as built - return 2nd copy for customers records per Mike T
Plan resubmittals received  1/8/2007  
INSP-Alarm Testing9/13/20069/13/20069/15/2006PPART
DetailsTroy Cobbley
A temporary occupancy was given for the basement mech. room. A/v's have been tested, smoke detectors and the sprinkler control valves for this same areas sprinkler system. The fire pump and related items are not ready yet.
FIR-Aging Inspection6/21/20066/21/20066/23/2006 NR
DetailsTroy Cobbley
Central tower work is in progress
Permit Ready to Issue  3/13/2006  
Inspection Record Card- Fire3/13/2006 3/13/2006 DONE
Telephone call  3/13/2006 DONE
left mess that permit is ready
Inspection Record Card- Fire3/13/2006 3/13/2006 DONE
Issue and Print Permit  3/13/2006 DONE
Plan assigned to (Mary)11/22/2005 3/11/2006 DONE
Alarm Plan Check  3/11/2006 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  3/11/2006 DONE
Plan resubmittals received  2/24/2006 DONE
Case Summary  2/24/2006 DONE
Alarm Plan Check  12/6/2005 FAIL
Faxed comments to Charlie Bayne. A complete review has not been completed.
Application received  11/22/2005  
Case Summary  11/22/2005 DONE