INSP-Final Inspection | 4/10/2006 | 4/11/2006 | 4/11/2006 | A | PASS |
Forrest France
|
|
|
Fire alarm functioned properly, inspection passed.
|
INSP-Final Inspection | 4/7/2006 | 4/10/2006 | 4/10/2006 | A | CANC |
Forrest France
|
|
|
we are now ready. Could you please call me when you have an approximate time you'll be out. Thanks, Harry ; Phone #: ###-#### Internet Inspection Request from: Harry Thompson Inspection cancelled from web by: Harry Thompson
|
INSP-Final Inspection | 4/6/2006 | 4/7/2006 | 4/7/2006 | A | CANC |
Forrest France
|
|
|
Forrest, This is ready again. Fire alarms guys used UVIR tester. Please call when you think you can be here. Thanks, Harry; Phone #: ###-#### Internet Inspection Request from: Harry Thompson Inspection cancelled from web by: Harry Thompson
|
INSP-Alarm Testing | 4/4/2006 | 4/6/2006 | 4/6/2006 | A | FAIL |
Forrest France
|
|
|
UV/IR detection device failed upon activation to shut down equipment and report as an alarm condition.
|
INSP-Final Inspection | 3/30/2006 | 4/4/2006 | 4/4/2006 | A | CANC |
Forrest France
|
|
|
Inspection for Tel Hood Fire supresion cabinet; Phone #: ###-#### Internet Inspection Request from: Harry Thompson Canceled per phone conversation with H. Thompson due to scheduling conflicts.
|
Issue and Print Permit | | | 11/25/2005 | | DONE |
|
|
|
|
Application received | | | 11/23/2005 | | DONE |
|
|
|
This permit was created on the web by Paul Marcolina
|
Plan assigned to (Mary) | 11/23/2005 | | 11/23/2005 | | DONE |
|
|
|
|
Alarm Plan Check | | | 11/23/2005 | | PASS |
|
|
|
Approved pending PDS Fire Inspector field verification. No comments written.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 11/23/2005 | | DONE |
|
|
|
|