INSP-Final Inspection | 3/1/2006 | 3/2/2006 | 3/2/2006 | A | PASS |
Forrest France
|
|
|
Requested corrections have been made, fire alarm tested satisfactory.
|
INSP-Final Inspection | 2/21/2006 | 2/23/2006 | 2/23/2006 | A | FAIL |
Forrest France
|
|
|
Need to reprogram existing under floor detectors for door release at the new roll-up fire door as discussed.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/13/2006 | | DONE |
|
|
|
|
Issue and Print Permit | | | 1/13/2006 | | DONE |
|
|
|
|
Plan assigned to (Mary) | 11/23/2005 | | 1/12/2006 | | DONE |
|
|
|
|
Alarm Plan Check | | | 1/12/2006 | | PASS |
|
|
|
Approved pending PDS Fire Inspector field verification. No comments written.
|
Application received | | | 11/23/2005 | | DONE |
|
|
|