INSP-Final Inspection | 4/27/2006 | 5/4/2006 | 5/4/2006 | A | PASS |
Forrest France
|
|
|
The required corrections have been made, fire sprinkler permit finaled.
|
Plan resubmittals received | | | 4/25/2006 | | DONE |
Bill Alexander
|
|
|
|
Sprinkler Plan Check | 4/25/2006 | | 4/25/2006 | | PASS |
Bill Alexander
|
|
|
Rerouting supply for Smock and Bootie area piping.
|
INSP-Final Inspection | 2/21/2006 | 2/23/2006 | 2/23/2006 | A | FAIL |
Forrest France
|
|
|
One head has not been installed, the field installation does not match approved plans, will require resubmittal reflecting changes.
|
Plan assigned to (Bill) | 11/23/2005 | | 12/14/2005 | | DONE |
|
|
|
|
Sprinkler Plan Check | 11/23/2005 | | 12/14/2005 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/14/2005 | | DONE |
|
|
|
|
Issue and Print Permit | | | 12/14/2005 | | DONE |
|
|
|
|
Application received | | | 11/23/2005 | | DONE |
|
|
|
This permit was created on the web by Paul Marcolina
|