INSP-Final Inspection | 12/27/2005 | 12/27/2005 | 12/27/2005 | P | PASS |
Forrest France
|
|
|
The permitted demo work is satisfactory, inspection passed.
|
(F) Reprint permit | | | 12/20/2005 | | DONE |
|
|
|
|
Sprinkler Plan Check | 12/15/2005 | | 12/16/2005 | | DONE |
Bill Alexander
|
|
|
|
Inspection Record Card- Fire | 12/16/2005 | | 12/16/2005 | | DONE |
|
|
|
|
Telephone call | | | 12/16/2005 | | DONE |
|
|
|
left mess that permit is ready
|
Plan resubmittals received | | | 12/15/2005 | | |
|
|
|
|
Issue permit | | | 12/8/2005 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 12/1/2005 | | 12/7/2005 | | DONE |
|
|
|
|
Sprinkler Plan Check | 12/1/2005 | | 12/7/2005 | | PART |
Bill Alexander
|
|
|
1. The installation of the backflow device and riser modifications will affect the system performance. Provide verification of system meeting Light Hazard Occupancy area/density of incorporating modifications and the added pressure loss of this manufacturer's backflow prevention device. BMC 7-01-50 IFC 901.2 and IFC 105.4)
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/7/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 12/7/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 12/7/2005 | | 12/7/2005 | | DONE |
|
|
|
|
Telephone call | | | 12/7/2005 | | DONE |
|
|
|
left mess that permit is ready
|
Application received | | | 12/1/2005 | | |
|
|
|
|