Permit Information
Permit NumberFIR05-00834
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 800 W IDAHO ST
Project Namealm - THE MODE BUILDING
Customer Number915212202
ePlanReview 
Description
To provide total notification and cooking hood monitoring for the remodeled space on the first floor to an existing required manual fire alarm system.

FIR05-00893 is associated with building permit BLD05-01998 which is to convert an existing 2,098 square foot tenant space located on the 1st story of the "Mode Building" into a restaurant. Work is to include interior nonbearing walls, two grease hoods, a dishwashing hood, millwork, and finishes. Any expansion of this tenant space in the future will require a separate permit. A license agreement with ACHD is required for the encroachment of ducts and equipment into the alley. A license is required from the City Clerk for the 290 square foot sidewalk seating area. The tenant shall contact the City Clerk's office directly for approval. The work shall comply with the approved drawings, the plan review report, and all applicable codes. The fire sprinkler system shall comply with NFPA 13 as regulated by the Fire Department. **CJW** (KOI JAPANESE RESTAURANT - MODE BLDG - 1ST STORY) This building is fire sprinklered to substitute for 1-hr fire-resistance rated construction.

FIR05-00834 is associated with building permit BLD05-02886 which is to expand an existing 2,098 square foot restaurant tenant space into an adjacent 1,218 square foot area. After the expansion, this tenant space will have a total floor area of about 3,316 square feet (2,136 square foot seating, 1,153 square foot kitchen/bar, 27 square foot office). This tenant space is located on the 1st story of the "Mode Building". Work within the existing restaurant tenant space was done under permit BLD05-01998. Work is to include interior nonbearing walls, a retractable partition, and finishes. The work shall comply with the approved drawings, the plan review report, and all applicable codes. Within the remodel area, the fire sprinkler system shall comply with NFPA 13 as regulated by the Fire Department. **CJW** (KOI JAPANESE RESTAURANT - PHASE II - THE MODE BLDG - 1ST STORY) The fire sprinklers substitute for 1-hr fire-resistive construction.

Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/15/20063/16/20063/16/2006APASS
DetailsForrest France
Fire alarm work is acceptable, inspection passed.
Inspection Record Card- Fire3/13/2006 3/13/2006 DONE
Permit Ready to Issue  3/13/2006  
Telephone call  3/13/2006 DONE
left mess that permit is ready
Issue and Print Permit  3/13/2006 DONE
Alarm Plan Check  3/11/2006 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  3/11/2006 DONE
Plan resubmittals received  2/27/2006  
Alarm Plan Check  2/17/2006 FAIL
The resubmittal was for a plan modification only. NO WRITTEN COMMENTS. Simplex did not address the manual pull station issue. (see comment #1) a resubmittal is required. I will accept revised plans and riser to place in the package.
Telephone call  2/17/2006 DONE
Notified Charlie Bayne of Simplex that a resubmittal is required to address comment #1 prior to final inspection.
Plan resubmittals received  1/31/2006  
(F) Reprint permit  1/18/2006 DONE
Issue and Print Permit  12/29/2005 DONE
Plan assigned to (Mary)12/6/2005 12/28/2005 DONE
Alarm Plan Check  12/28/2005 PART
Partial; (a resubmittal will be required prior to final inspection) pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  12/28/2005 DONE
Permit Ready to Issue  12/28/2005 DONE
Inspection Record Card- Fire12/28/2005 12/28/2005 DONE
Telephone call  12/28/2005 DONE
Left voice message for Charlie that permit is ready & fees///12/28/05 @3:15pm BAS
Stop Work/Reinspection Fee 12/19/200512/19/2005 DONE
A stop work order has been placed as the fire alarm wire has been routed without a FIR permit. A double fee will be accrued.
Plan resubmittals received  12/16/2005 DONE
Alarm Plan Check  12/14/2005 FAIL
A previous FA permit FIR01-00170 (Simplex-Grinnell) comments state a manual fire alarm system is required in the building. Therefore, the FA system shall be upgraded to code on a TI by TI basis. I have phoned Charlie Bayne at Simplex-Grinnell and he is aware that a resubmittal is required. (TI space only)
Application received  12/6/2005  
Case Summary  12/6/2005 DONE