Permit Information
Permit NumberFIR05-00835
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 1055 N CURTIS RD
Project Namealm - Mobile MRI
Customer Number914692614
ePlanReview 
Description
To provide a fire alarm input for a "panic" switch that will be located in the mobile MRI unit. The input shall activate a "priority 2" for SARMC personnel to respond to. When the MRI unit is "mobile", the input will have a EOL to ensure they do not have false inputs. No written comments. Battery calculations appear to be sufficient. The PDS Fire Inspector shall field verify both functionality of the "panic" switch and that the input clears when the EOL is installed.

There is no associated building permit
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/2/20062/3/20062/3/2006PPASS
DetailsTroy Cobbley
Permit finaled.
Issue and Print Permit  12/15/2005 DONE
Permit Ready to Issue  12/14/2005 DONE
Inspection Record Card- Fire12/14/2005 12/14/2005 DONE
Telephone call  12/14/2005 DONE
Left voice message for Charlie that told that permit is ready & fees///12/14/05 @ 8:26am BAS
Plan assigned to (Mary)12/6/2005 12/13/2005 DONE
Alarm Plan Check  12/13/2005 PASS
Approved pending PDS Fire Inspector field verification. No comments written.
PLANS/APPL TAKEN TO FRONT DESK  12/13/2005 DONE
Case Summary  12/6/2005 DONE
Application received  12/6/2005