INSP-Final Inspection | 3/14/2006 | 3/15/2006 | 3/15/2006 | P | PASS |
Troy Cobbley
|
|
|
Permit finaled
|
INSP-Sprinkler Rough-in/Hydro | 2/27/2006 | 2/28/2006 | 2/28/2006 | A | PASS |
Troy Cobbley
|
|
|
Above ground hydro test passed. The test was witnessed by the general contractor. Need to get copy of test papers.
|
INSP-Sprinkler Rough-in | 2/27/2006 | 2/28/2006 | 2/28/2006 | A | PART |
Troy Cobbley
|
|
|
Need to provide one additional pipe hanger on the 1" armover over the north offices. Provide revised hydraulic calculations for 127sq. ft. sprinkler spacing. Provide certification for the backflow and forward flush. Provide tag for riser.
|
INSP-Sprinkler Rough-in/Hydro | 2/1/2006 | 2/1/2006 | 2/1/2006 | P | PASS |
Troy Cobbley
|
|
|
Underground hydro and flush passed
|
Issue and Print Permit | | | 12/28/2005 | | DONE |
|
|
|
|
Plan assigned to (Bill) | 12/7/2005 | | 12/22/2005 | | DONE |
|
|
|
|
Sprinkler Plan Check | 12/7/2005 | | 12/22/2005 | | PASS |
Bill Alexander
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/22/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 12/22/2005 | | 12/22/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 12/22/2005 | | DONE |
|
|
|
|
Case Summary | | | 12/7/2005 | | DONE |
|
|
|
|
Application received | | | 12/7/2005 | | |
|
|
|
|