Permit Information
Permit NumberFIR05-00840
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 101 S CAPITOL BLVD Unit: 703
Project NameSPR US BANK-7TH FLR
Customer Number 
ePlanReview 
Description
(VOLT INFORMATION SCIENCES - STE 703 - RESTROOM UPGRADE - LOBBY REMODEL - US BANK BLDG) This building is fire sprinklered because it is a high-rise. To replace all 133 existing pendant fire sprinklers throughout this permit and the entire remaining floor from standard response to quick response. Also to relocate some existing drops and add 2 quick response SSU's; all for the creation of a 1,559 square foot office tenant space on the 7th story of an existing high rise building (19 total stories). To upgrade the 7th story core restrooms to be accessible to the disabled. To remodel the 7th story elevator lobby. The floor area of the entire 7th story is about 14,600 square feet. The "core" has a floor area of about 2,670 square feet. Work is to include interior nonbearing walls, suspended ceilings, interior doors, interior windows, and finishes. The fire sprinkler system, fire alarm system, and high-rise life safety systems (and the infrastructure supporting these systems) for the 7th story are required to comply with the provisions of the 2000 IBC. Existing systems shall be upgraded where necessary, including the installation of quick-response fire sprinklers. If not already existing, fire-safing shall be installed at the perimeter of the 7th story between the floor and the spandrel glass. The work shall comply with the approved drawings, the plan review report, and all applicable codes. The fire sprinkler system shall comply with NFPA 13 as regulated by the Fire Department. This permit is attached to BLD05-03058.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/10/20065/10/20065/10/2006PPASS
DetailsForrest France
Permitted scope of sprinkler work is complete, upgrade agreement letter verified for compliance.
INSP-Sprinkler Rough-in3/14/20063/14/20063/14/2006PFAIL
DetailsForrest France
Pendent heads at the remainder of the vacant floor area have been changed to quick response, however no drop ceiling is installed, heads are at various heights AFF, spacing is irregular, final pending compliance with the upgrade agreement per permit review notes.
INSP-Final Inspection1/5/20061/5/20061/5/2006PPART
DetailsForrest France
Fire sprinkler work for the TI space is satisfactory, need to verify agreement for the adjacent unoccupied area fire sprinkler upgrade prior to final-see review notes for comments.
INSP-Final Inspection1/3/20061/4/20061/4/2006APART
DetailsForrest France
One arm-over in the exit corridor by the SW stairs needs a hanger, per contractor the heads in the corridor to be relocated to center of ceiling tile per request by owner, some escutcheons in the elevator lobby have sheetrock mud on them.
INSP-Sprinkler Rough-in12/28/200512/28/200512/28/2005PPART
DetailsForrest France
Overhead rough-in is good for cover at the drop ceiling areas in the TI space and the hard lid ceiling at the lobby, the corridor and restroom areas not complete at this time.
Issue and Print Permit  12/28/2005 DONE
Plan assigned to (Bill)12/7/2005 12/23/2005 DONE
Plan resubmittals received  12/23/2005 DONE
Inspection Record Card- Fire12/23/2005 12/23/2005 DONE
Permit Ready to Issue  12/23/2005 DONE
Telephone call  12/23/2005 DONE
left mess that permit is ready
Sprinkler Plan Check12/22/2005 12/22/2005 FAIL
DetailsTroy Cobbley
Plans failed. Comments faxed to contractor
PLANS/APPL TAKEN TO FRONT DESK  12/22/2005 DONE
Telephone call  12/22/2005 DONE
left mess for tom that permit failed and needs to be picked up
Application received  12/7/2005  
Sprinkler Plan Check12/23/2005    
DetailsBill Alexander