Permit Information
Permit NumberFIR05-00841
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 5477 N QUAIL SUMMIT PL
Project NameSPR HIGHLAND HOME
Customer Number 
ePlanReview 
Description
HIGHLAND HOMES LLC * To install a (modified) life safety NFPA 13D system in a five bedroom, four bathroom 4,116-f/2 two story single family dwelling (2,466-ft/2 first floor/1650-ft/2 second floor) with a attached 882-ft/2 three car garage. The modification is the installation of a single row of dry sidewall sprinklers along the common wall attached to the garage and the living space. System shall be equipped with an alarm initiating device and an outside alarm. All fire sprinkler work and related, which includes dual use, single service water supply, the system backflow prevention device (provided by others), shall be per NFPA 13D, approved plans, engineering/red-lining and attached review comments, under direction of the Fire Chief. This permit is attached to: BLD04-02054.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/17/20064/18/20064/18/2006APASS
DetailsTroy Cobbley
Fire sprinkler permit finaled
INSP-Final Inspection4/13/20064/14/20064/14/2006AFAIL
DetailsTroy Cobbley
No city approved plans on site for inspection. The pendant head in the kitchen still exceeds 10' from the exterior wall. Pendant head in the upper bedroom exceeds 10' from wall. Light and ceiling fans are obstructing pendants in upper and lower bedrooms. Pendant head in den is blocked by arched entry into small connecting foyer (must be atleast 6' away). Need to pipe drain to exterior and provide correct orfice for testing. Underground has not been flushed yet. There may be other items that are addressed on the approved plans but was unable to verify due to missing plans.
INSP-Final Inspection4/12/20064/13/20064/14/2006PCANC
DetailsTroy Cobbley
Would it be possible to have this inspection around noon. James is the contact @ ###-####. Thanks; Phone #: ###-#### Internet Inspection Request from: Trent Bice
INSP-Sprinkler Rough-in1/10/20061/11/20061/11/2006APART
DetailsForrest France
Overhead rough-in is acceptable to cover pending corrections as noted on plans including overspaced head at kitchen, overspaced head at 2nd floor hall, install head at master bathroom as indicated, the backflow device installed is not as submitted (provide correct device or verify calcs are the same), tenting at cold cavity areas is satisfactory.
PLANS/APPL TAKEN TO FRONT DESK  1/10/2006 DONE
Permit Ready to Issue  1/10/2006 DONE
Inspection Record Card- Fire1/10/2006 1/10/2006 DONE
Telephone call  1/10/2006 DONE
Trent called and asked if permit is ready, I told him yes so they will pick up this afternoon///1/10/06 @11:45am BAS
Issue and Print Permit  1/10/2006 DONE
Plan assigned to (Bill)1/4/2006 1/10/2006 DONE
Sprinkler Plan Check1/6/2006 1/10/2006 PASS
DetailsBill Alexander
Plan resubmittals received  1/6/2006 DONE
DetailsBill Alexander
Sprinkler Plan Check12/23/2005 1/4/2006 FAIL
DetailsBill Alexander
1. Design Test Area #1 (First Level) is flawed. The minimum for Tyco Series "LFII", Res., Concealed, SSP, 4.2 K-factor, TY2596 head is per the manufacturers listing, Table "A", as a function for temperature ratings and maximum allowable coverage area. Revise and resubmit full plans with revised calculations any unclarified plan corrections of t he following Items, (which are not crossed out AND/OR addressed to be verified by Inspector).

2. Plans are incomplete and lack clarity to determine minimum protection requirement (i.e. columns, etc.). It would appear that the "Bonus Room" is constructed over the "Garage"? If this is correct, and it actually is; then the garage separation from living space requirement is lacking, since the garage protection does not extend to all (ceiling) exposures of the "Bonus Room" living space and plan corrections by resubmittal are required. (Subdivision Plat Requirements, BMC 7-01-50, IFC 901.2)

3. Plan is incomplete. Second level bathroom between Bedrooms #2 and #3, plans does not show minimum separation requirements addressed in 4.1.2. If not separated, then fire sprinkler protection will be required. Clarify with detailed construction separation/protection and resubmit.

4. Shower area of the master bath is part of the bathroom and will require fire sprinkler protection coverage. Revise and resubmit. (NFPA 13D-4.1.2)

5. Kitchen appears to have a pantry located in the south corner? If this is the case, it is not exempt and will require fire sprinkler protection. Clarify, revise and resubmit.

6. Riser detail is incorrect. Relocate the domestic control and install it upstream of the fire sprinkler take-off (no exceptions), which should have been included in the calcs. The backflow valves shall require minimum monitoring per 7.1.2.3[a]. Revise and resubmit. BMC 7-01-50, IFC 901.2, IFC 105.4.2).

7. Riser is addressed as having exposed CPVC. Exposed risers shall meet minimum requirement for the pipe listing addressed for "System Risers in NFPA 13D Applications:"
a. The residential pendant head located within 12" of the riser.
b. The Riser needs supported within 2'-0" of the ceiling.
c. Vertical lines shall be supported at intervals described in #7 thru 10 of the manufacturer's installation requirements.
d. Maximum distance from the wall/s and the outside surface of the riser pipe shall be 1½".
e. Listed CPVC solvent cement shall be used.
f. Supports of riser shall be per section 9.2.5 of NFPA 13-2002 edition.
Correct, revise and resubmit.
Miscellaneous action  1/4/2006 DONE
Took failed documents ti the permit desk for calling and returning.
Telephone call  1/4/2006 DONE
left mess for trent bice that plans have failed & need to resubmit
Case Summary  12/23/2005 DONE
Plan resubmittals received  12/23/2005  
INSP-Sprinkler Rough-in12/21/200512/22/200512/22/2005AFAIL
DetailsTroy Cobbley
Provide letter for installation prior to approved plans to bill, resubmit plans with piping changes. No inspection performed.
Issue and Print Permit  12/21/2005 DONE
Plan assigned to (Bill)12/7/2005 12/20/2005 DONE
Sprinkler Plan Check12/7/2005 12/20/2005 PART
DetailsBill Alexander
The data has been moved to a Word document attached to this case.
PLANS/APPL TAKEN TO FRONT DESK  12/20/2005 DONE
Inspection Record Card- Fire12/20/2005 12/20/2005 DONE
Permit Ready to Issue  12/20/2005 DONE
Telephone call  12/20/2005 DONE
left mess that permits is ready
Case Summary  12/7/2005  
Application received  12/7/2005