Permit Information
Permit NumberFIR05-00842
StatusFinaled
Name DEBEST FIRE PROTECTION
Site Address 755 W BROAD ST
Project NameBODO BLDG #8 - SPR
Customer Number 
ePlanReview 
Description
(T-3 WIRELESS - BODO BLDG #8 - 1ST STORY) This building is fire sprinklered because it is a high-rise building. To add 6 SSU's, 2 SSP's and relocate 6 existing SSU's for the creation of a 793-ft/2 retail sales tenant space located on the 1st floor of an 11 story high-rise building. Fire sprinkler work is related to new interior nonbearing walls, suspended ceilings and a restroom. The work is required to comply with the approved drawings, the plan review report, and all applicable codes. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD05-03007.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/21/20073/22/20073/22/2007APASS
DetailsForrest France
Fire sprinkler permit finaled.
INSP-Final Inspection3/23/20063/24/20063/24/2006APART
DetailsTroy Cobbley
Fire sprinkler can be finaled when shell core is ready
Issue and Print Permit  3/16/2006 DONE
Sprinkler Plan Check2/21/2006 3/15/2006 PASS
DetailsBill Alexander
Corrections/Verifications Required:
1. This floor has 274 - Viking Model "Microfast", Q.R., SSU, 5.6 K-factor, (½"), VK300 of which this tenant area is adding 2 more. These sprinklers are not listed for pressures in excess of 175 psi. This tenant shall be fitted with approve SSU fire sprinklers that meet the shell systems current performance pressure performance design available with IFC Fire/Life Safety Inspector verifying by submittals and installation matching the same. (NFPA 13-6.13)

2. All pipe and fittings incorporating in this tenant shall also be required to meet the 13-6.1.3 and 6.4.4. Data submittals shall also be required to the IFC Fire/Life Safety Inspector matching the existing and new modification addressed under this permit.

3. This facility has a fire pump and maximum static or flowing pressure exceeds 100 psi. Branch line above a ceiling supplying pendent sprinklers below the ceiling shall have hanger assemblies on all end or offset sprinkler, to prevents upward movement of the pipe. (NFPA 13-9.2.3.4.3.1)

4. Occupancy is not permitted until FIR05-00425 incorporating the High Rise with secondary water supply has been finaled.
Miscellaneous action  3/15/2006 DONE
Took revised plans to permit desk for releasing. 2nd review, no fees.
Case Summary  3/15/2006 DONE
Telephone call  3/15/2006  
Informed Catherine (Debest Fire Protection) ###-#### to pick up permit; permit previously issued, scope has not changed, 2nd review - no fee per Bill Alexander 3-15-06 eus
Permit Ready to Issue  3/15/2006  
Inspection Record Card- Fire3/15/2006 3/15/2006 DONE
Plan resubmittals received  2/21/2006  
INSP-Sprinkler Rough-in2/16/20062/17/20062/17/2006AFAIL
DetailsForrest France
The approved stamped plans do not reflect the actual field installation, a drop ceiling is indicated on approved plans, however the space has been completed and installed with uprights for an OTS ceiling. As installed the uprights are blocked by beams and overspaced in certain locations, need to remove the uprights above the restroom hard lids, provide plan resubmittal reflecting accurate information regarding construction details and correct sprinkler layout prior to next inspection.
Permit Ready to Issue  12/21/2005 DONE
Inspection Record Card- Fire12/21/2005 12/21/2005 DONE
Telephone call  12/21/2005 DONE
left mess that permit is ready
Issue and Print Permit  12/21/2005  
Plan assigned to (Bill)12/7/2005 12/20/2005 DONE
Sprinkler Plan Check12/7/2005 12/20/2005 PASS
DetailsTroy Cobbley
Approved as noted. No written comments.
PLANS/APPL TAKEN TO FRONT DESK  12/20/2005 DONE
Application received  12/7/2005