Information based on query as of Tuesday, July 16, 2024.
Permit Information
Permit NumberFIR05-00848
StatusFinaled
Name AUDIO ELECTRONICS INC
Site Address 802 W BANNOCK ST
Project Namealm - HOFF BLDG-1ST FLR
Customer Number 
ePlanReview 
Description
To provide total notification and total area coverage (automatic detection) in the 1st TI space and the entire 11th floor. The existing required manual fire alarm system includes sprinkler monitoring, HVAC shutdown, elevator recall/shutdown fire/smoke damper control and all items required for a high rise.

FIR05-00848 is associated with building permit BLD05-03075 which is to remodel an existing 1417 sq ft bank located on the ground floor per approved plans. Work to include demolition of an existing vestibule, removal of storefront glazing and installation of new ATM Machine, add new teller line, miscellaneous related interior finishes. This building is fully fire sprinklered any alterations to the sprinkler system WILL require a separate permit and shall be installed per NFPA #13 as regulated by the fire department. (rmh)- (Mountain West Bank)* (-HOFF BLDG-1ST FLR)*

FIR05-00849 is associated with building permit BLD05-02816 which is to remodel a 2,533 square foot whole floor tenant space located on the 11th story of the Hoff Building. Work is to include a 4 inch high platform, a ramp, interior nonbearing walls, a suspended ceiling, lever type hardware on all doors, and interior finishes. A total coverage fire detection system is required to be installed on the 11th story in accordance with NFPA 72 as part of this project. A separate permit is required. The fire detection system is required be tied to the building fire alarm system so that if smoke were detected anywhere on this floor, at least this entire floor will be alarmed. The work shall comply with the approved drawings, the plan review report, and all applicable codes. Alterations to the fire sprinkler system shall comply with NFPA 13 as regulated by the Fire Department. **CJW** (MOUNTAIN WEST BANK - HOFF BLDG - 11TH STORY) This building is required to be fire sprinklered because it is a high-rise.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/5/20061/6/20061/6/2006APASS
DetailsForrest France
Required corrections have been completed, fire alarm permit finaled.
INSP-Final Inspection1/3/20061/4/20061/4/2006AFAIL
DetailsForrest France
Strobe notification devices are not in synchronization within the TI space or within view of the adjacent common area strobes, still need to provide an updated map at the panel as requested, not all smoke alarms tested at this time.
INSP-Final Inspection12/29/200512/30/200512/30/2005PFAIL
DetailsForrest France
The two wall mounted strobes are below 80" AFF, need to provide an updated building map at the panel, not a complete inspection at this time.
INSP-Final Inspection12/29/200512/29/200512/29/2005PCANC
DetailsForrest France
Forrest, We would like to schedule this for late this afternoon. 1st floor only. Call if their are any problems. Thanks Jason or Mike; Phone #: ###-#### Internet Inspection Request from: Jason Minnick Inspection cancelled from web by: Jason Minnick
Plan assigned to (Mary)12/9/2005 12/29/2005 DONE
Alarm Plan Check  12/29/2005 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  12/29/2005 DONE
Permit Ready to Issue  12/29/2005 DONE
Inspection Record Card- Fire12/29/2005 12/29/2005 DONE
Telephone call  12/29/2005 DONE
Spoke with Jason and told him that permit is ready & fees///12/29/05 @8:00am BAS
Issue permit  12/29/2005 DONE
Plan resubmittals received  12/19/2005 DONE
Case Summary  12/19/2005 DONE
Alarm Plan Check  12/16/2005 FAIL
Resubmittal required. Faxed comments to Jason Minnick.
Application received  12/9/2005  
Case Summary  12/9/2005 DONE