INSP-Final Inspection | 1/5/2006 | 1/6/2006 | 1/6/2006 | A | PASS |
Forrest France
|
|
|
Required corrections have been completed, fire alarm permit finaled.
|
INSP-Final Inspection | 1/3/2006 | 1/4/2006 | 1/4/2006 | A | FAIL |
Forrest France
|
|
|
Strobe notification devices are not in synchronization within the TI space or within view of the adjacent common area strobes, still need to provide an updated map at the panel as requested, not all smoke alarms tested at this time.
|
INSP-Final Inspection | 12/29/2005 | 12/30/2005 | 12/30/2005 | P | FAIL |
Forrest France
|
|
|
The two wall mounted strobes are below 80" AFF, need to provide an updated building map at the panel, not a complete inspection at this time.
|
INSP-Final Inspection | 12/29/2005 | 12/29/2005 | 12/29/2005 | P | CANC |
Forrest France
|
|
|
Forrest, We would like to schedule this for late this afternoon. 1st floor only. Call if their are any problems. Thanks Jason or Mike; Phone #: ###-#### Internet Inspection Request from: Jason Minnick Inspection cancelled from web by: Jason Minnick
|
Plan assigned to (Mary) | 12/9/2005 | | 12/29/2005 | | DONE |
|
|
|
|
Alarm Plan Check | | | 12/29/2005 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/29/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 12/29/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 12/29/2005 | | 12/29/2005 | | DONE |
|
|
|
|
Telephone call | | | 12/29/2005 | | DONE |
|
|
|
Spoke with Jason and told him that permit is ready & fees///12/29/05 @8:00am BAS
|
Issue permit | | | 12/29/2005 | | DONE |
|
|
|
|
Plan resubmittals received | | | 12/19/2005 | | DONE |
|
|
|
|
Case Summary | | | 12/19/2005 | | DONE |
|
|
|
|
Alarm Plan Check | | | 12/16/2005 | | FAIL |
|
|
|
Resubmittal required. Faxed comments to Jason Minnick.
|
Application received | | | 12/9/2005 | | |
|
|
|
|
Case Summary | | | 12/9/2005 | | DONE |
|
|
|
|