INSP-Final Inspection | 1/9/2006 | 1/9/2006 | 1/10/2006 | P | PASS |
Forrest France
|
|
|
Items on c/n have been completed and retested, fire alarm passed final inspection.
|
INSP-Final Inspection | 1/6/2006 | 1/6/2006 | 1/6/2006 | P | FAIL |
Forrest France
|
|
|
Addressing at two smoke detectors does not match between map and panel for correct location, EOL voltage is too low for min. requirements on battery backup, cd rating at one strobe in the open area has been changed from a 60 as shown on approved plans to a 110.
|
Plan assigned to (Mary) | 12/9/2005 | | 12/29/2005 | | DONE |
|
|
|
|
Alarm Plan Check | | | 12/29/2005 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 12/29/2005 | | DONE |
|
|
|
|
Permit Ready to Issue | | | 12/29/2005 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 12/29/2005 | | 12/29/2005 | | DONE |
|
|
|
|
Telephone call | | | 12/29/2005 | | DONE |
|
|
|
Spoke with Jason & told him that permit is ready & fees///12/29/05 @8:00am BAS
|
Issue permit | | | 12/29/2005 | | DONE |
|
|
|
|
Plan resubmittals received | | | 12/19/2005 | | DONE |
|
|
|
|
Case Summary | | | 12/19/2005 | | DONE |
|
|
|
|
Plan resubmittals received | | | 12/19/2005 | | DONE |
|
|
|
|
Alarm Plan Check | | | 12/16/2005 | | FAIL |
|
|
|
Resubmittal required. Faxed comments to Jason Minnick.
|
Case Summary | | | 12/9/2005 | | DONE |
|
|
|
|
Application received | | | 12/9/2005 | | |
|
|
|
|