Permit Information
Permit NumberFIR05-00854
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 1395 W PARKHILL DR
Project NameSPR PARKHILL RESIDENCE
Customer Number 
ePlanReview 
Description
PARKHILL RESIDENCE * To install a (modified) life safety NFPA 13D system in a new five bedroom, three and half bathroom 3756-FT/2 two story single family dwelling (2,391-ft/2 first floor/1,365-ft/2 second floor and a 1,098-ft/2 three car garage. System shall also be equipped with an alarm initiating device and an outside alarm. All fire sprinkler work and related, which includes dual use, single service water supply, the system backflow prevention device (provided by others), shall be per NFPA 13D, approved plans, engineering/red-lining and attached review comments, under direction of the Fire Chief. This permit is attached to: BLD05-00854.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/20/20067/20/20067/20/2006PPASS
DetailsForrest France
C/N items have been verified for completion, OH piping flushed per contractor, permit finaled.
INSP-Final Inspection7/18/20067/19/20067/19/2006APART
DetailsForrest France
Need to provide test certification for the backflow preventer prior to final, need to secure main control valves as required. Also NOTE: The overhead system piping was connected and filled using the UG supply prior to field inspection of the UG line flush as required, sprinkler contractor is aware of code violation. Line flush performed post OH system fill. Remaining final inspection items are satisfactory.
INSP-Supply line flush7/14/20067/18/20067/19/2006ANH
DetailsForrest France
Please call Brian Johansen (Johanson Plumbing) Prior to arrival. This is a public utility line servicible only by utility contractor.; Phone #: ###-#### Internet Inspection Request from: Trent Bice Called contact number and left a message, no return phone call was made to coordinate inspection time, no inspection performed.
INSP-Final Inspection7/12/20067/13/20067/13/2006ACANC
DetailsTroy Cobbley
James said he is not ready.
INSP-Final Inspection6/27/20066/28/20066/27/2006ACANC
DetailsForrest France
Could we get this inspection around 9:30 am. James is the contact @###-####. Thanks; Phone #: ###-#### Internet Inspection Request from: Trent Bice Inspection cancelled from web by: Trent Bice
INSP-Sprinkler Rough-in2/17/20062/21/20062/21/2006APART
DetailsForrest France
Lacking proper coverage at one "closet " area on the first floor, tenting has been adjusted at one bedroom location, the remainder of overhead rough-in is good for cover, possible light fixture obstructions at certain locations depending on the fixture dimentions.
Issue and Print Permit  2/15/2006 DONE
Plan assigned to (Bill)1/25/2006 2/14/2006 DONE
DetailsBill Alexander
Sprinkler Plan Check1/25/2006 2/14/2006 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  2/14/2006 DONE
Inspection Record Card- Fire2/14/2006 2/14/2006 DONE
Telephone call  2/14/2006 DONE
left mess that permit is ready
Permit Ready to Issue  2/14/2006  
Plan resubmittals received  1/25/2006  
Plan assigned to (Bill)12/12/2005 1/24/2006 DONE
Sprinkler Plan Check1/6/2006 1/24/2006 PART
DetailsBill Alexander
1. Calculation/Design is flawed. Area #2 heads are designed for 12'-0" X 12'-0" with 13 gpm and required 9.6 psi which is insufficient. Reference the manufacturers head listing information, revise and resubmit for approval. (BMC 7-01-50-901.2, IFC 105.4.2)
January 24, 2006 - Redesign information not provided. Provide corrections as requested and resubmit.

2. Plan is incorrect/incomplete. Riser Detail, Key Notes and calculations do not correlate.
a. The riser is 1¼" with steel and CPVC. Also it is imperative that the designer read, know and understand all additional requirements for exposed CPVC risers which are clearly explained and in the manufacturers listed installation requirements for CPVC (not just a single head within 1'-0" of the riser). These requirements must be addressed (included) in your design and on the PLANS.
January 24, 2006 - Not addressed. One issue is that the maximum distance between the wall(s) and the outside surface of the riser pipe shall be 1-1/2". Your design/plan shows 1'-0"? This may be since the section detail is in a partition, and the view is facing the garage wall? That is why sections cuts should be provided with the cut line on the floor plan (basic Sprinkler 101), so code determination can be verified prior to installation and inspection.
b. Provide a domestic control connected UPSTREAM of the fire sprinkler take-off, which SHALL be been included in the calcs with no exceptions allowed. (NFPA 13D-A.6.2[a], A.6.3[a] BMC 7-01-50, IFC 901.2, IFC 105.4.2).
January 24, 2006 - Not provided.

3. Underground supply shown on the plan is incomplete since it does not address the pipe size, length and type from the street to the meter? Provide plans that are complete and correlate with calculation, which shall include, but may not be limited too:
b. *Elevation changes on any underground that lifts from the street to inside the home.
January 24, 2006 - Not addressed. (*It shall be assumed FLAT or DOWNHILL).
c. Plan shall include location and size of the main supply in the street.
January 24, 2006 - Not provided or readdressed as: "New 1½" polyethylene Pipe"?
d. Calculations shall then correlate with all of the above.
January 24, 2006 - Not provided due to item #1 above.

4. Plan is incomplete. Plans shall include included:
a. Bathroom dimensioning (ft/2).
January 24, 2006 - Not provided "Powder" room on the first floor?

f. Under stairs construction shall be addressed on the plans or sprinklers shall be required.

5. It would appear that the second level sits over a portion of the garage, yet designer's plans do not clearly indicate this as being so? No information provided as how the piping or heads in the garage are going to be maintained or kept at, or higher than the minimum 40ºF, which is required to prevent possible damage and maintain system operation per code. (BMC 7-01-50-901.2, IFC 105.4.2, 104.9, A.8.6.4)
January 24, 2006 - Plan detailed information is still lacking.
(BMC 7-01-50-901.2, IFC 105.4.2, NFPA 13D 4.1.2, 8.6.2)
January 24, 2006 - Not provided or addressed.

6. Alarm information provided is obsolete, not current and does not meet the Boise Municipal Code. Reference the BMC 7-01-57 IFC 903.3.1.3.1.
January 24, 2006 - Not addressed. Please Boise Municipal ordinance addresses the minimum requirement under Section 7-01-57 AMENDMENT ADDING SECTION 903.3.1.3.1 "NFPA 13D SPRINKLER ALARMS" Add a Section 903.3.1.3.1, which may be found at: http://www.cityofboise.org/city_clerk/citycode/0701.pdf
PLANS/APPL TAKEN TO FRONT DESK  1/24/2006 DONE
DetailsBill Alexander
Inspection Record Card- Fire1/24/2006 1/24/2006 DONE
Permit Ready to Issue  1/24/2006  
Telephone call  1/24/2006 DONE
tlk to rent bice ###-#### that partial approval and permit is ready to be picked up
Issue and Print Permit  1/24/2006 DONE
Plan resubmittals received  1/6/2006 DONE
Sprinkler Plan Check12/12/2005 12/30/2005 FAIL
DetailsBill Alexander
The data has been moved to a Word document attached to this case.
Miscellaneous action  12/30/2005 DONE
Returned failed plans/documents to the front desk for returning for corrections.
Telephone call  12/30/2005 DONE
talked to trent bice -plans failed & will pickup
Application received  12/12/2005