Permit Information
Permit NumberFIR05-00859
StatusFinaled
Name DEBEST FIRE PROTECTION
Site Address 12501 W EXPLORER DR
Project NameSPR SAKSON & TAYLOR
Customer Number 
ePlanReview 
Description
SAKSON & TAYLOR * To modify the existing system by relocate 15 and add 3 pendants sprinkler in the remodel of an existing 5,712-ft/2 tenant space, for a new office. Fire sprinkler work is related to the removal of interior partitions to create larger open office, the construction of new interior partitions, and the installation of new suspended ceiling system with related lighting, and HVAC registers. This building is fully fire sprinklered. This fire protection work shall comply with the IFC 2003 and the permit review comments; each regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to BLD05-3164.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/20/20061/20/20061/20/2006PCANC
DetailsForrest France
Duplicate inspection request, inspection completed this AM.
INSP-Final Inspection1/19/20061/20/20061/20/2006APASS
DetailsForrest France
Fire sprinkler work is satisfactory, the requested corrections have been made.
INSP-Final Inspection1/9/20061/9/20061/9/2006PCANC
DetailsTroy Cobbley
Rough In and Final; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley
PLANS/APPL TAKEN TO FRONT DESK  1/4/2006 DONE
Inspection Record Card- Fire1/4/2006 1/4/2006 DONE
Permit Ready to Issue  1/4/2006 DONE
Telephone call  1/4/2006 DONE
left mess that permit is ready
Issue permit  1/4/2006 DONE
Plan assigned to (Bill)12/13/2005 1/3/2006 DONE
Plan resubmittals received  1/3/2006  
Sprinkler Plan Check1/3/2006 1/3/2006 PASS
DetailsBill Alexander
Per revised comments.
Sprinkler Plan Check12/13/2005 12/30/2005 FAIL
DetailsBill Alexander
The hydraulic calculations were provided to prove a maximum 225-ft/2 spacing and that two pendant heads piped from the same 1” outlet. The problems found this submittal is that the two heads off of 1” outlet have been proven off 1½” branchline piping and nothing for 1¼" (reference copy and storage room 115 & 116)? Also the calcs for the lines feeding two heads off 1" are on the 1" outlet flowing through separate 1" armover piping? A node should have been added off the armover tee, so both heads are actually flowing though the same 1" armover pipe!

System layout/design does not meet minimum code. Fire sprinkler protection requires the wetting of all walls. Provide corrected plans meeting minimum fire protection requirements. (BMC 7-01-50:901.2, IFC 105.4.2, 106, 107.2.2, 901.6, 903.3.3)

There are areas where existing and new heads are installed which do not meet the minimum 6'-0" spacing distance between standard spray sprinklers. (NFPA 13:8.5.3.4, 8.6.3.4.1)
Application received  12/13/2005  
Case Summary  12/13/2005 DONE