Permit Information
Permit NumberFIR05-00863
StatusFinaled
Name NORTHWEST SALES COMPANY
Site Address 11818 W JOPLIN RD
Project Namealm - digester control bldg
Customer Number 
ePlanReview 
Description
To replace the existing FACP. This is a voluntary manual fire alarm system that includes non-required full area detection and notification throughout. The compressor room is classified as a Class1, Div2, therefore intrinsic barriers and explosion proof devices/appliances are required.

There is no associated building permit.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/5/20085/6/20085/6/2008APASS
DetailsTroy Cobbley
Permit finaled
Case Summary  2/22/2008 DONE
INSP-Final Inspection4/24/20074/24/20074/24/2007PFAIL
DetailsTroy Cobbley
Need breaker lock and the fire alarm strobes conflict with the existing building alarm. They either need to sync, the existing system deactivated or blocked from view as discussed. Also need the associated quick permit called in.
INSP-Final Inspection4/23/20074/24/20074/23/2007ACANC
DetailsTroy Cobbley
LET ME KNOW WHEN YOU CAN BE THERE... Phone #: ###-#### Internet Inspection Request from: Rick Groom Inspection cancelled from web by: Rick Groom
FIR-Aging Inspection4/12/20064/12/20064/12/2006 NR
DetailsTroy Cobbley
Per Dave he is waiting on Boise City.
Issue and Print Permit  1/11/2006 DONE
Alarm Plan Check  12/27/2005 PASS
Approved pending field inspection of fire alarm permit comments.
PLANS/APPL TAKEN TO FRONT DESK  12/27/2005 DONE
Inspection Record Card- Fire12/27/2005 12/27/2005 DONE
Permit Ready to Issue  12/27/2005 DONE
Telephone call  12/27/2005 DONE
called ###-#### and told Rick that permit is ready and fees
Case Summary  12/14/2005 DONE
Application received  12/14/2005  
Plan assigned to (Mary)12/14/2005