INSP-Final Inspection | 5/5/2006 | 5/8/2006 | 5/9/2006 | A | PASS |
Forrest France
|
|
|
Corrections have been verified, fire alarm permit passed inspection.
|
INSP-Final Inspection | 4/27/2006 | 5/4/2006 | 5/4/2006 | A | FAIL |
Forrest France
|
|
|
Need to provide smoke detection at the double doors for release of mag locks per NFPA 72 2002, audibility appears to be inadequate at some locations as discussed and noted on plan review documents. Damper smoke detection, pull stations, EOL, and visual notification tested okay.
|
Issue and Print Permit | | | 3/13/2006 | | |
|
|
|
|
Alarm Plan Check | | | 3/10/2006 | | PASS |
|
|
|
Plan Modification. Approved pending PDS Fire Inspector field verification. No comments written.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 3/10/2006 | | DONE |
|
|
|
|
INSP-Final Inspection | 2/21/2006 | 2/23/2006 | 2/23/2006 | A | PART |
Forrest France
|
|
|
Audio/visual and duct detection devices tested satisfactory for the vending/break room and the smoking break room only for a portion of this permit.
|
Plan assigned to (Mary) | 12/24/2005 | | 2/17/2006 | | DONE |
|
|
|
|
Alarm Plan Check | | | 2/17/2006 | | PASS |
|
|
|
The submittal is acceptable on the revised set. At this time, the approved set of drawings has not been stamped, I will stamp them on Thursday 2/23. The PDS Fire Inspector to field verify. Please call me if you need clarification prior to the inspection.
|
Issue and Print Permit | | | 2/17/2006 | | DONE |
|
|
|
|
Alarm Plan Check | | | 1/12/2006 | | FAIL |
|
|
|
1) Plans need to include door hold-opens.
2) Need to include a mounting detail for the smoke detectors on the FSD.
3) Question of enough audibility in the office area
|
Application received | | | 12/14/2005 | | DONE |
|
|
|