Permit Information
Permit NumberFIR05-00876
StatusFinaled
Name SIMPLEX/GRINNELL
Site Address 11580 W FAIRVIEW AVE
Project NameSPR COLTRIN CENTRAL VACUUM
Customer Number908376602
ePlanReview 
Description
(COLTRIN CENTRAL VACUUM)(COLTRIN BLDG) This building is constructed for Nonseparated Uses per IBC Section 302.3.1. This building is fully fire sprinklered for area increase and story increase. To add and relocate fire sprinklers in a new 4,000-ft/2 office tenant with some storage in a vacant first floor area of an existing two story 18,490-ft/2 shell building that was constructed under BLD04-02020. This fire sprinkler work is related to new interior walls, new gypsum board ceilings and soffit work, some new suspended ceiling work, the creation of two new restrooms, per plans which may include red-lined notes, attached plan review conditions, regulated by the Fire Chief. The review comments, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. Shell and underground supply fire protection work (Overhead FIR05-00312 and Underground FIR05-00222), must be finaled prior to this permits acceptance. This permit is attached to BLD05-03008.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/16/20062/16/20062/16/2006PPASS
DetailsTroy Cobbley
permit finaled
INSP-Final Inspection2/7/20062/7/20062/7/2006PPART
DetailsTroy Cobbley
A temporary occupancy was given with Dave Hannemans permission until issues with the shell building have been corrected. Permit is ready to final when that happens.
INSP-Sprinkler Rough-in1/24/20061/25/20061/25/2006AFAIL
DetailsTroy Cobbley
Insulation backing is still laying on some of the heads in the east wing and the dry system piping in the second floor area has been covered without re-inspection. Backing needs fixed and the second floor backing removed so the piping can be inspected. "Do Not Cover" sticker was placed at the door.
INSP-Sprinkler Rough-in1/17/20061/17/20061/17/2006PFAIL
DetailsTroy Cobbley
Need to add on upright head just to the west of the main entry and fix all of the falling insulation and backing.
Plan assigned to (Bill)12/19/2005 12/21/2005 DONE
Sprinkler Plan Check12/19/2005 12/21/2005 PASS
DetailsBill Alexander
PLANS/APPL TAKEN TO FRONT DESK  12/21/2005 DONE
Permit Ready to Issue  12/21/2005 DONE
Inspection Record Card- Fire12/21/2005 12/21/2005 DONE
Issue and Print Permit  12/21/2005 DONE
Case Summary  12/19/2005 DONE
Application received  12/19/2005