INSP-Final Inspection | 3/6/2007 | 3/7/2007 | 3/7/2007 | A | PASS |
Forrest France
|
|
|
Final fire alarm inspection passed, permit finaled.
|
FIR-Aging Inspection | 3/6/2007 | 3/6/2007 | 3/6/2007 | P | DONE |
Forrest France
|
|
|
Final inspection scheduled.
|
INSP-Final Inspection | 7/12/2006 | 7/13/2006 | 7/13/2006 | P | FAIL |
Troy Cobbley
|
|
|
Need print out of the signals sent and updated plans showing the additional tamper switches.
|
Telephone call | | | 7/12/2006 | | DONE |
|
|
|
Recieved phone request from Protex representative, Terry, requesting a copy of the issued plans. Explains that their issued set of plans has been lossed. Currently tracking down plans.
|
CHANGE STATUS TO (ISS) | | | 6/1/2006 | | DONE |
|
|
|
paid fee and picked up permit
|
(F) Reprint permit | | | 6/1/2006 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 5/31/2006 | | 5/31/2006 | | DONE |
|
|
|
|
Telephone call | | | 5/31/2006 | | DONE |
|
|
|
lft ms for rob ahten ###-#### that permit and fees are ready to be picked up
|
Permit Ready to Issue | | | 5/31/2006 | | DONE |
|
|
|
|
Alarm Plan Check | | | 5/30/2006 | | PASS |
|
|
|
Plan Modification. Approved pending field inspection of fire alarm permit comments.
|
PLANS/APPL TAKEN TO FRONT DESK | | | 5/30/2006 | | DONE |
|
|
|
|
Plan resubmittals received | | | 5/26/2006 | | DONE |
|
|
|
Received resub of two sets of plans with application.
|
INSP-Final Inspection | 3/8/2006 | 3/10/2006 | 3/10/2006 | A | PART |
Forrest France
|
|
|
c/n items have been completed, all items tested except two AHU detectors which are not installed at this time, provide signage on the door to the FACP.
|
INSP-Final Inspection | 3/2/2006 | 3/6/2006 | 3/6/2006 | A | PART |
Forrest France
|
|
|
7 AHU duct smoke detectors tested okay, 2 AHU detectors are not installed at this time, a ceiling will be required at the riser/FACP room which will require relocation and testing of the SD at the panel, need to test flow switches at the main riser (contractor unable to flow water at this time), tamper switch at antifreeze system point #6 needs adjustment, need to test low air and the WPI tamper at south riser as contractor had not made preparation to do so, provide signage at the door to the FACP.
|
Issue and Print Permit | | | 1/11/2006 | | DONE |
|
|
|
|
Plan assigned to (Mary) | 12/20/2005 | | 1/10/2006 | | DONE |
|
|
|
|
PLANS/APPL TAKEN TO FRONT DESK | | | 1/10/2006 | | DONE |
|
|
|
|
Alarm Plan Check | | | 1/10/2006 | | PASS |
|
|
|
Approved pending field inspection of fire alarm permit comments.
|
Permit Ready to Issue | | | 1/10/2006 | | DONE |
|
|
|
|
Inspection Record Card- Fire | 1/10/2006 | | 1/10/2006 | | DONE |
|
|
|
|
Telephone call | | | 1/10/2006 | | DONE |
|
|
|
Spoke with Terie and told her that permit is ready & fees///1/10/06 @2:25pm BAS
|
Alarm Plan Check | | | 1/4/2006 | | FAIL |
|
|
|
faxed comments to Rob Ahten.
|
Plan resubmittals received | | | 1/4/2006 | | |
|
|
|
|
Case Summary | | | 12/20/2005 | | |
|
|
|
|
Application received | | | 12/20/2005 | | |
|
|
|
|